Plan Review Notes
Plan Review Notes For Permit 19050603
Permit Number 19050603
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-09 06:26:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE COMMENTS FROM PREVIOUS REVIEW; NOT ADDRESSED
 (PROVIDE DOCUMENTATION TO DEMONSTRATE THAT THIS IS NOT
 A SUBSTANTIAL IMPROVEMENT). THIS CAN BE SENT VIA EMAIL.
  
 2. A.02 AND OTHER PAGES, PLEASE CLARIFY, CONFERENCE
 ROOM DOOR, PULL SIDE APPEARS TO HAVE A COLUMN
 OBSTRUCTING THE REQUIRED 18" MANEUVERING CLEARANCE
 REQUIRED BY FBC A FIGURE 404.2.4.1(A). IF THIS IS NOT A
 COLUMN, PLEASE ADVISE VIA EMAIL AND THE PLAN WILL BE
 STAMPED WITH REDLINE/PROVISO. IF THIS IS A COLUMN,
 REVISE PLAN.
  
 NOTE THAT THE COPY ROOM ALSO HAS THE SAME CONDITION. IF
 ARCHITECT FEELS THIS IS COVERED BY AN EXCEPTION (WORK
 AREA), PROVIDE RATIONALE IN A LETTER. FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
  
  
  
  
  
  