| Plan Review Notes For Permit 19050603 |
| Permit Number |
19050603 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-07-09 06:26:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SEE COMMENTS FROM PREVIOUS REVIEW; NOT ADDRESSED | | | (PROVIDE DOCUMENTATION TO DEMONSTRATE THAT THIS IS NOT | | | A SUBSTANTIAL IMPROVEMENT). THIS CAN BE SENT VIA EMAIL. | | | | | | 2. A.02 AND OTHER PAGES, PLEASE CLARIFY, CONFERENCE | | | ROOM DOOR, PULL SIDE APPEARS TO HAVE A COLUMN | | | OBSTRUCTING THE REQUIRED 18" MANEUVERING CLEARANCE | | | REQUIRED BY FBC A FIGURE 404.2.4.1(A). IF THIS IS NOT A | | | COLUMN, PLEASE ADVISE VIA EMAIL AND THE PLAN WILL BE | | | STAMPED WITH REDLINE/PROVISO. IF THIS IS A COLUMN, | | | REVISE PLAN. | | | | | | NOTE THAT THE COPY ROOM ALSO HAS THE SAME CONDITION. IF | | | ARCHITECT FEELS THIS IS COVERED BY AN EXCEPTION (WORK | | | AREA), PROVIDE RATIONALE IN A LETTER. FEEL FREE TO | | | CONTACT ME TO DISCUSS. | | | | | | | | | | | | | | | | | | | | | |
|