Plan Review Notes
Plan Review Notes For Permit 19050603
Permit Number 19050603
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-22 15:15:325/22/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 05 - THERE IS AN INDICATION OF A
 RANGE/STOVE/VENT WITHIN THE KITCHEN.
  
 IS THIS KITCHEN RANGE/STOVE/VENT FUNCTION OR JUST FOR
 SHOW?
  
 PLEASE PROVIDE A NOTE OF NON-FUNCTIONAL OR DETAILS OF
 FUNCTION AS APPLICABLE.
  
  
  
 3) SHEET M 02 - - THERE ARE INDICATIONS OF 4 A/C UNITS
 OF 2000 CFM
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
  
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4
 ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN
 APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE
 FOLLOWING SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
  
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  