| 2020-04-06 10:36:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| | PERMITTED. AS THERE IS ANOTHER STRUCTURE ON THIS |
| | PROPERTY, THIS SECOND STRUCTURE WOULD NEED TO BE FEED |
| | FROM THAT ORIGINAL SERVICE. WHILE ANOTHER METER CAN IS |
| | PERMITTED TO BE INSTALLED FOR THIS STRUCTURE, IT MUST |
| | BE FEED FROM THE EXISTING SERVICE, UNLESS ONE OF THE |
| | EXCEPTIONS TO NEC 230.2 APPLY. PROVIDE CORRECTION |
| | AND/OR CLARIFICATION. WPB FBC 107.2.1; NEC 230.2; FBC |
| | RE E3601.2 (YOUR RESPONSE LETTER STATES THIS IS ZONED |
| | MULTI-FAMILY. ACCORDING TO PBC PAPA, THIS IS ZONED |
| | 0-100 SINGLE FAMILY. PROVIDE CORRECTIONS AS NECESSARY |
| | TO COMPLY WITH CODE.) |
| | 2. PROVIDE ACCURATE LOAD CALCULATION FOR MAIN SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 (SEE COMMENT 1 RESPONSE, PROVIDE CORRECTIONS AS |
| | NECESSARY TO COMPLY WITH CODE.) |
| | 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE TO |
| | REMODELED STRUCTURE, INCLUDE EXISTING AND NEW LOADS TO |
| | CONFIRM CAPACITY OF SERVICE IS ADEQUATE. THE LOAD |
| | CALCULATION PROVIDED SHOWS A REQUIRED LOAD OF 218 AMPS, |
| | BUT THE SERVICE SPECIFIED IS 150 AMP. THIS IS NOT |
| | SUFFICIENT TO CARRY THE LOAD CALCULATED, BUT IT APPEARS |
| | THE LOAD WAS NOT CALCULATED CORRECTLY. NEC 215.2, 220, |
| | 408.30; FBC RE E3602.2 (LOAD CALCULCATION FOR REMODELED |
| | STRUCTURE IS SATISFACTORY, BUT THE LOAD REQUIRED FOR |
| | THE MAIN SERVICE NEEDS TO BE SUPPLIED BASED ON COMMENTS |
| | 1 AND 2. ADDITIONALLY, THE PANEL SCHEDULE SHOWS A |
| | STANDARD WATER HEATER WHEN A TANKLESS IS SPECIFIED IN |
| | THE LOAD CALCULATION. CORRECT DISCREPANCY AND PROVIDE |
| | LOAD CALCULATION FOR THE 100 AMP PANEL TO CONFIRM IT |
| | HAS THE CAPACITY FOR THIS LOAD.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 (NOT PROVIDED.) |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. RISER DIAGRAM SHOWS #4 WIRE FEEDING A 100 AMP |
| | PANEL. THIS WIRE SIZE IS NOT RATED FOR 100 AMPS. |
| | PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE E3705.1 |
| | (THE WIRE SIZE WAS UPDATED, BUT NOW THE RISER SHOWS |
| | THREE # 1 WIRES AND ONE # 8 WIRE IN A 1 INCH CONDUIT. |
| | THIS CONDUIT IS NOT SIZED PROPERLY FOR THE CAPACITY OF |
| | WIRE. PROVIDE CORRECTION. NEC CHAPTER 9 TABLES) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6742 |
| | [email protected] |
| | |