Plan Review Notes
Plan Review Notes For Permit 19050597
Permit Number 19050597
Review Stop E
Sequence Number 3
Notes
Date Text
2020-02-25 09:32:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. AS THERE IS ANOTHER STRUCTURE ON THIS
 PROPERTY, THIS SECOND STRUCTURE WOULD NEED TO BE FEED
 FROM THAT ORIGINAL SERVICE. WHILE ANOTHER METER CAN IS
 PERMITTED TO BE INSTALLED FOR THIS STRUCTURE, IT MUST
 BE FEED FROM THE EXISTING SERVICE, UNLESS ONE OF THE
 EXCEPTIONS TO NEC 230.2 APPLY. PROVIDE CORRECTION
 AND/OR CLARIFICATION. WPB FBC 107.2.1; NEC 230.2; FBC
 RE E3601.2 (YOUR RESPONSE LETTER STATES THIS IS ZONED
 MULTI-FAMILY. ACCORDING TO PBC PAPA, THIS IS ZONED
 0-100 SINGLE FAMILY. PROVIDE CORRECTIONS AS NECESSARY
 TO COMPLY WITH CODE.)
 2. PROVIDE ACCURATE LOAD CALCULATION FOR MAIN SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2 (SEE COMMENT 1 RESPONSE, PROVIDE CORRECTIONS AS
 NECESSARY TO COMPLY WITH CODE.)
 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE TO
 REMODELED STRUCTURE, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. THE LOAD
 CALCULATION PROVIDED SHOWS A REQUIRED LOAD OF 218 AMPS,
 BUT THE SERVICE SPECIFIED IS 150 AMP. THIS IS NOT
 SUFFICIENT TO CARRY THE LOAD CALCULATED, BUT IT APPEARS
 THE LOAD WAS NOT CALCULATED CORRECTLY. NEC 215.2, 220,
 408.30; FBC RE E3602.2 (LOAD CALCULCATION FOR REMODELED
 STRUCTURE IS SATISFACTORY, BUT THE LOAD REQUIRED FOR
 THE MAIN SERVICE NEEDS TO BE SUPPLIED BASED ON COMMENTS
 1 AND 2. ADDITIONALLY, THE PANEL SCHEDULE SHOWS A
 STANDARD WATER HEATER WHEN A TANKLESS IS SPECIFIED IN
 THE LOAD CALCULATION. CORRECT DISCREPANCY AND PROVIDE
 LOAD CALCULATION FOR THE 100 AMP PANEL TO CONFIRM IT
 HAS THE CAPACITY FOR THIS LOAD.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. RISER DIAGRAM SHOWS #4 WIRE FEEDING A 100 AMP
 PANEL. THIS WIRE SIZE IS NOT RATED FOR 100 AMPS.
 PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE E3705.1
 (THE WIRE SIZE WAS UPDATED, BUT NOW THE RISER SHOWS
 THREE # 1 WIRES AND ONE # 8 WIRE IN A 1 INCH CONDUIT.
 THIS CONDUIT IS NOT SIZED PROPERLY FOR THE CAPACITY OF
 WIRE. PROVIDE CORRECTION. NEC CHAPTER 9 TABLES)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  