Plan Review Notes
Plan Review Notes For Permit 19050597
Permit Number 19050597
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-15 07:52:13PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE A COMPLETE SCOPE OF WORK NARRATIVE. PLUMBING
 APPLICATION IS LISTING TANKLESS WATER HEATER AS SCOPE
 OF WORK BUT THE PLANS ARE LEADING ME TO BELIEVE THAT
 ALL PLUMBING PIPING AND FIXTURES ARE BEING REPLACED.
 PLEASE CLARIFY. FBC 107.2.1
  
 1A) BASE ON PLANS SCOPE OF WORK THE TOTAL STATED VALUE
 SEEMS LOW. PROVIDE A SIGN BONA FIDE CONTRACT WPB AMEND
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) PLUMBING PERMIT APPLICATION IS CALLING OUT FOR A
 TANKLESS WATER HATER BUT R405-2017 FORM LIST 40 GALLON
 TANKLESS @ E.F OF .92. PLEASE CLARIFY WHICH HEATER IS
 BEING USED AND PROVIDE COMPLETE MANUFACTURES
 INSTALLATION MANUAL TO INCLUDE THE HEAT RISE AND
 EFFICIENCY OF UNIT. STORAGE TANK WATER HEATER SHALL
 HAVE A MIN E.F OF .97. FBC-ENERGY R403.5.6.2, C404.2
  
 3) PLUMBING ISOMETRIC DRAWING SHOW THE TOILET AS 2"( 3"
 MIN IS REQUIRED) FBC-P 709.1 AND THE WASHING MACHINE
 SHALL NOT DISCHARGE INTO THE BATHROOM GROUP WET
 VENT(FBC-P 912.1 AND SHALL BE VENTED FBC-P 901.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  