| Date |
Text |
| 2019-05-15 07:52:13 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) PROVIDE A COMPLETE SCOPE OF WORK NARRATIVE. PLUMBING |
| | APPLICATION IS LISTING TANKLESS WATER HEATER AS SCOPE |
| | OF WORK BUT THE PLANS ARE LEADING ME TO BELIEVE THAT |
| | ALL PLUMBING PIPING AND FIXTURES ARE BEING REPLACED. |
| | PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 1A) BASE ON PLANS SCOPE OF WORK THE TOTAL STATED VALUE |
| | SEEMS LOW. PROVIDE A SIGN BONA FIDE CONTRACT WPB AMEND |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) PLUMBING PERMIT APPLICATION IS CALLING OUT FOR A |
| | TANKLESS WATER HATER BUT R405-2017 FORM LIST 40 GALLON |
| | TANKLESS @ E.F OF .92. PLEASE CLARIFY WHICH HEATER IS |
| | BEING USED AND PROVIDE COMPLETE MANUFACTURES |
| | INSTALLATION MANUAL TO INCLUDE THE HEAT RISE AND |
| | EFFICIENCY OF UNIT. STORAGE TANK WATER HEATER SHALL |
| | HAVE A MIN E.F OF .97. FBC-ENERGY R403.5.6.2, C404.2 |
| | |
| | 3) PLUMBING ISOMETRIC DRAWING SHOW THE TOILET AS 2"( 3" |
| | MIN IS REQUIRED) FBC-P 709.1 AND THE WASHING MACHINE |
| | SHALL NOT DISCHARGE INTO THE BATHROOM GROUP WET |
| | VENT(FBC-P 912.1 AND SHALL BE VENTED FBC-P 901.2.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |