Plan Review Notes
Plan Review Notes For Permit 19050597
Permit Number 19050597
Review Stop M
Sequence Number 1
Notes
Date Text
2019-05-24 10:34:46MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE ANTI-THEFT PORTS AT CU.
 M1411.8 LOCKING ACCESS PORT CAPS.
  
 2. PROVIDE EXHAUST FAN ROOFTOP DETAIL FOR FLAT ROOF.
 M1501.1OUTDOOR DISCHARGE.
 THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM
 SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH
 SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE.
  
 3. PROVIDE AN ACCURATELY COMPLETED ENERGY SUBMITTAL.
 3A. SUBMITTAL SHOWS 40 GAL WATER HEATER, PLAN SHOWS
 TANKLESS WATER HEATER.
 3B. PLANS SPECIFY CARRIER EQUIPMENT, MANUAL J SPECIFIES
 GOODMAN EQUIPMENT.
 3C. OWNER/AGENT SHALL SIGN ENERGY SUBMITTAL.
 3D. BUILDER SHALL SIGN EPL CARD.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  