| 2019-05-24 11:00:10 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON |
| | RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. |
| | |
| | THIS PROPERTY IS ZONED SINGLE FAMILY WITH 2 UNITS PER |
| | THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE. DUE |
| | TO THE LIMITATIONS OF . WPB FBC 107.2.1; NEC 230.2; FBC |
| | RE E3601.2 WHICH LIMITS ONLY ONE SERVICE PER |
| | RESIDENTIAL ADDRESS, PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION FOR THE 2ND UNIT ON THIS PROPERTY: |
| | |
| | 1. LOAD CALCULATIONS OF 2ND STRUCTURES PANEL. NEC 220; |
| | FBC RE E3602.2. |
| | |
| | 2. FEEDER CONDUCTOR SIZING. NEC 225.30 A BUILDING OR |
| | OTHER STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR |
| | FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING |
| | MEANS SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH |
| | CIRCUIT.. |
| | |
| | 3. LOCATION OF ELECTRICAL SERVICE PANEL ON 2ND |
| | STRUCTURE. NEC 230.70, 250.6; FBC RE E3601.6 |
| | CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| | DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE. |
| | PROVIDE A MAIN ON THE OUTSIDE OF THE HOME. |
| | |
| | 4. RISER DIAGRAHM SHOWING THE GROUNDING ELCTRODE |
| | SYSTEM. NEC 250.32; FBC RE E3607.3 |
| | A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. |
| | |
| | NO COMPREHENSIVE REVIEW WAS PERFORMED AT THIS TIME,. |
| | CLARIFICATION IS REQUIRED FOR THE ABOVE INFORMATION. |
| | |
| | |
| | |
| | |