2019-05-24 11:00:10ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 THIS PROPERTY IS ZONED SINGLE FAMILY WITH 2 UNITS PER
 THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE. DUE
 TO THE LIMITATIONS OF . WPB FBC 107.2.1; NEC 230.2; FBC
 RE E3601.2 WHICH LIMITS ONLY ONE SERVICE PER
 RESIDENTIAL ADDRESS, PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR THE 2ND UNIT ON THIS PROPERTY:
  
 1. LOAD CALCULATIONS OF 2ND STRUCTURES PANEL. NEC 220;
 FBC RE E3602.2.
  
 2. FEEDER CONDUCTOR SIZING. NEC 225.30 A BUILDING OR
 OTHER STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR
 FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING
 MEANS SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH
 CIRCUIT..
  
 3. LOCATION OF ELECTRICAL SERVICE PANEL ON 2ND
 STRUCTURE. NEC 230.70, 250.6; FBC RE E3601.6
 CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR
 DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE.
 PROVIDE A MAIN ON THE OUTSIDE OF THE HOME.
  
 4. RISER DIAGRAHM SHOWING THE GROUNDING ELCTRODE
 SYSTEM. NEC 250.32; FBC RE E3607.3
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING.
  
 NO COMPREHENSIVE REVIEW WAS PERFORMED AT THIS TIME,.
 CLARIFICATION IS REQUIRED FOR THE ABOVE INFORMATION.
  
  
  
  