| Date |
Text |
| 2019-06-05 06:42:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY |
| | THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CLEAR |
| | LOCATION AND DIAGRAMS OF EACH SIGN. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 |
| | |
| | INFORMATIONAL NOTE: PROVIDE NOTE ON PLANS INDICATING |
| | SIGNS WILL BE CONTROLLED BY A ASTROMICAL TIMECLOCK PER |
| | EXTERIOR LIGHTING CONTROLS REQUIREMENTS OF THE FBC EC |
| | 405.2.4 |
| | |
| | DISCONNECT REQUIREMENTS FOR EACH SIGN MUST CONFORM TO |
| | NEC 600.6A1. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |