| 2019-07-29 11:29:50 | 1) SHT. A-2 - THE GRAB BAR REINFORCING DETAIL FOR THE |
| | SHOWER SHALL COMPLY WITH THE FAIR HOUSING ACT GUIDLINES |
| | FIGURE #5. THE BACKING SHALL BE LOCATED 32 INCHES |
| | MAXIMUM TO THE BOTTOM OF THE BACKING. SHOW THAT THE 32 |
| | INCHES IS MAXIMUM ON THE PLANS. |
| | 2) THE WIDTH OF THE BACKING SHALL BE A MAXIMUM OF 6 |
| | INCHES PER THE FHA GUIDELINES FIGURE #5, NOT 18 INCHES |
| | AS SHOWN ON THE PLANS. THE DETAIL NOTES A 2 X 6 METAL |
| | TRACK PIECE ALSO. CLARIFY. |
| | 3) THE MAXIMUM CABINET HEIGHT FOR A SPECIFICATION TYPE |
| | "B" BATHROOM IS 34 INCHES PER THE FHA GUIDELINES. THE |
| | MASTER BATH ELEVATION DETAILS #4 & #5 ON SHT. A-3 SHOWS |
| | 36 INCHES TO THE TOP OF THE VANITY. |
| | 4) SHT. A-1 - NOTE # 9 STATES AN EXISTING TUB IS TO BE |
| | REMOVED AND A NEW TUB CONNECTED TO EXISTING PLUMBING |
| | YET SHEETS A-2 & P-1 SHOW A NEW SHOWER. CLARIFY. |
| | 5) THE REINFORCEMENT DETAIL FOR THE GRAB BARS IN THE |
| | SHOWER ON SHT. A-2 SHALL BE LOCATED ON BOTH SIDE WALLS |
| | AND THE BACK WALL BUT IS ONLY SHOWN ON THE BACK WALL ON |
| | THE DETAIL. CLARIFY. |
| | 6) INDICATE THE GAUGE OF THE METAL TO BE USED FOR THE |
| | REINFORCEMENT FOR THE SHOWER GRAB BARS. THE METAL SHALL |
| | BE ABLE TO SUPPORT A LOAD OF 250 LBF. |
| | 7) CLARIFY THE DISTANCE BETWEEN THE WALL AND THE |
| | KITCHEN CORNER COUNTER. THE WIDTH SHALL BE 40 INCHES |
| | CLEAR YET THE DIMENSION LINE ON THE PLAN APPEARS TO |
| | ENCROACH INTO THE REFRIGERATOR AND POSSIBLY THE STOVE. |
| | REVISE THE DIMENSION LINE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |