| 2019-05-16 10:08:00 | PLUMBING 1ST REVIEW**DENIED** BUILDING WAS CONSTRUCTED |
| | IN 2006 UNDER THE FAIR HOUSING ACT** ALL CODE |
| | REFERENCES ARE FROM THE FAIR HOUSING DESIGN MANUAL |
| | EXCEPT COMMENT #6 WHICH COMES FROM FBC PLUMBING. |
| | |
| | 1) PROVIDE WHAT DESIGN UNDER THE FAIR HOUSING ACT (FHA) |
| | YOUR BATHROOM IS DESIGNED FROM, PROVIDE EXISTING GUEST |
| | BATHROOM DESIGN SPEC. NOTE IF EXISTING IS SPEC A THEN |
| | BOTH BATHROOM SHALL BE REQUIRED TO BE SPEC A DESIGN.FBC |
| | 107.3.5 |
| | |
| | 2) PROVIDE CLEAR FLOOR SPACE FOR ALL FIXTURES AS |
| | REQUIRED BY FHA TO INCLUDE EXISTING TO ENSURE YOUR NEW |
| | DESIGN COMPLIES WITH FHA 7.39. FBC 107.2.1 |
| | |
| | 3) PROVIDE DETAIL OF SHOWER GRAB BAR BACKING TO BE |
| | INSTALLED. NOTE GRAB BARS THEM SELF ARE NOT REQUIRED TO |
| | BE INSTALLED JUST THE ABILITY FOR THE UNIT TO BE |
| | ADAPTABLE. FHA 6.3, 6.12 |
| | |
| | 4) PROVIDE CABINET HEIGHT DETAIL FOR BOTH BATHROOM SINK |
| | AND KITCHEN SINK SHOWING THEY COMPLY. MAX 34" BATHROOM, |
| | MAX 36" KITCHEN. FHA 7.52, 7.15 |
| | |
| | 5) PROVIDE MEASUREMENT ON PLAN BETWEEN WALL AND KITCHEN |
| | COUNTER CORNER SHOWING MIN CLEARANCE OF 40" IS PROVIDE |
| | FOR ACCESSIBILITY INTO THE KITCHEN. FHA 7.7 |
| | |
| | 6) PROVIDE LOCATION OR NOTE ON PLAN THAT THE SHUT OFF |
| | VALVES FOR THE WASHING MACHINE SHALL BE ACCESSIBLE TO |
| | COMPLY WITH FBC-P 606.3 |
| | |
| | |