| 2019-06-05 06:14:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE UL OR OTHER NRTL LISTINGS FOR ALL PROPOSED |
| | EQUIPMENT. PPC'S, ANTENNAS, CABINETS, "STEALTH |
| | ENCLOSURES" ETC. NEC 90.7, 110.2, 110.3B FBC 107.2.1 |
| | |
| | 2. PROVIDE LOAD CALCULATION OF EXISING 3000AMP SERVICE |
| | TO INCLUDE ALL LOADS, EXISING AND NEW. LOAD STUDY |
| | PROVIDED IS 1.5 YEARS OLD. FBC 107.2.1 NEC 220. |
| | |
| | 3. NO CONDUCTOR SIZES PROVIDED TO FEED NEW METER BANK |
| | ENCLOSURE? NEW METER BANK WILL TIE INTO EXISITING? MORE |
| | INFORMATION REQUIRED. FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |