| 2019-06-03 07:32:38 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. 553.79(5) 2016, THIS APPEARS TO BE A THRESHOLD |
| | BUILDING. EITHER ADDRESS THE FOLLOWING WHICH ARE |
| | REQUIRED FOR THRESHOLD BUILDINGS, OR SEND AN EMAIL |
| | EXPLAINING WHY THIS IS NOT THRESHOLD. |
| | |
| | A. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| | CONTRACTOR. |
| | |
| | B. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| | PROPOSED INSPECTORS. |
| | |
| | C. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT |
| | REQUIRED BY FS553.79(7)(D). |
| | |
| | (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS CHAPTER 553 AND CHAPTER 633. |
| | |
| | 2. IF THIS IS A THRESHOLD BUILDING, A THRESHOLD |
| | INSPECTION PLAN REQUIRED, FS553.79(5)A). SHEET S1.0 |
| | INCLUDES AN INSPECTION PLAN, REVISE TO CLARIFY THAT |
| | THIS IS THE THRESHOLD INSPECTION PLAN, OR PROVIDE ONE. |
| | |
| | 3. THE STRUCTURAL ENGINEER JAMES E. NOVAK, PE DOES NOT |
| | HAVE A TITLE BLOCK AS REQUIRED BY FS471, REVISE |
| | STRUCTURAL PAGES TO INCLUDE. PLEASE NOTE THAT THE |
| | CERTIFICATE OF AUTHORIZATION IS REQUIRED TO BE INCLUDED |
| | IN THE TITLE BLOCK. |
| | |
| | 4. CLARIFY LOCATION OF WORK. THE ADDRESS ON THE PLAN IS |
| | 700 S ROSEMARY; APPLICATION IS FOR 701 S ROSEMARY, FBC |
| | 107. |
| | |
| | 5. REVISE PLAN TO STATE WHICH METHOD OF COMPLIANCE IS |
| | SELECTED, FBC EB 301.1, ALONG WITH A BASIC CODE SUMMARY |
| | (NUMBER OF STORIES, BUILDING TYPE, GOVERNING CODE, |
| | OCCUPANCY CLASSIFICATION). |
| | |
| | 6. FBC B 1604.5, IF THIS BUILDING INCLUDES ASSEMBLY |
| | OCCUPANT LOAD OVER 300, RISK CATEGORY SHOULD BE III |
| | RATHER THAN II; EITHER REVISE SHEET S1.0 OR REVISE PLAN |
| | IF NECESSARY TO CLARIFY OCCUPANCY CLASSIFICATION AND |
| | OCCUPANT LOAD. |
| | |
| | 7. FBC 107, 703.2.1, EITHER REVISE PLAN TO INCLUDE THE |
| | UL ASSEMBLY OR PROVIDE THE ASSEMBLY SPECS. ALSO CONFIRM |
| | THAT THE ASSEMBLY PROPOSED MEETS THE REQUIREMENT OF FBC |
| | B 703.2.1. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |