Plan Review Notes
Plan Review Notes For Permit 19050582
Permit Number 19050582
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-03 07:32:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. 553.79(5) 2016, THIS APPEARS TO BE A THRESHOLD
 BUILDING. EITHER ADDRESS THE FOLLOWING WHICH ARE
 REQUIRED FOR THRESHOLD BUILDINGS, OR SEND AN EMAIL
 EXPLAINING WHY THIS IS NOT THRESHOLD.
  
 A. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 B. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 C. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D).
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 2. IF THIS IS A THRESHOLD BUILDING, A THRESHOLD
 INSPECTION PLAN REQUIRED, FS553.79(5)A). SHEET S1.0
 INCLUDES AN INSPECTION PLAN, REVISE TO CLARIFY THAT
 THIS IS THE THRESHOLD INSPECTION PLAN, OR PROVIDE ONE.
  
 3. THE STRUCTURAL ENGINEER JAMES E. NOVAK, PE DOES NOT
 HAVE A TITLE BLOCK AS REQUIRED BY FS471, REVISE
 STRUCTURAL PAGES TO INCLUDE. PLEASE NOTE THAT THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED TO BE INCLUDED
 IN THE TITLE BLOCK.
  
 4. CLARIFY LOCATION OF WORK. THE ADDRESS ON THE PLAN IS
 700 S ROSEMARY; APPLICATION IS FOR 701 S ROSEMARY, FBC
 107.
  
 5. REVISE PLAN TO STATE WHICH METHOD OF COMPLIANCE IS
 SELECTED, FBC EB 301.1, ALONG WITH A BASIC CODE SUMMARY
 (NUMBER OF STORIES, BUILDING TYPE, GOVERNING CODE,
 OCCUPANCY CLASSIFICATION).
  
 6. FBC B 1604.5, IF THIS BUILDING INCLUDES ASSEMBLY
 OCCUPANT LOAD OVER 300, RISK CATEGORY SHOULD BE III
 RATHER THAN II; EITHER REVISE SHEET S1.0 OR REVISE PLAN
 IF NECESSARY TO CLARIFY OCCUPANCY CLASSIFICATION AND
 OCCUPANT LOAD.
  
 7. FBC 107, 703.2.1, EITHER REVISE PLAN TO INCLUDE THE
 UL ASSEMBLY OR PROVIDE THE ASSEMBLY SPECS. ALSO CONFIRM
 THAT THE ASSEMBLY PROPOSED MEETS THE REQUIREMENT OF FBC
 B 703.2.1.
  
  
  
  
  
  
  
  
  
  