Plan Review Notes
Plan Review Notes For Permit 19050536
Permit Number 19050536
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-20 10:04:17MET ON THE PROJECT WITH ALL PERSONNEL INVOLVED WITH THE
 PROPOSED DE-STRESSING AND REMOVAL OF THE (4) POST
 TENSION TENDONS LOCATED UNDER THE 18TH FLOOR SLAB.
 THESE EXPOSED TENDONS WERE ENGINEERED AND INSTALLED TO
 SUPPORT ADDITIONAL LOADS AT MID-SPANS OF THE STRUCTURAL
 COLUMNS. THE FOLLOWING WAS DISCUSSED:
  
 1) A QUALIFIED STRUCTURAL ENGINEER SHALL SUBMIT AN
 EVALUATION AND CALCULATIONS OF THE EXISTING CONDITION
 OF THE CONCRETE FLOOR SLABS OF THE 17TH AND 18TH
 LEVELS.
  
 2) IF REQUIRED BY THE STRUCTURAL ENGINEER, SHORING AND
 RESHORING SHALL BE INSTALLED WITHIN THE WORK AREA AS
 INDICATED ON THE PLAN. A SHORING ENGINEER SHALL PROVIDE
 THE DESIGN OF THE SHORING/RESHORING INSTALLATION.
  
 3) THE EXTERIOR INFILL WALLS AND GLAZING SHALL BE
 PROTECTED PRIOR TO PERFORMING ANY DE-STREEING
 PROCEDURES.
  
 4) ALL AFORE-MENTIONED DOCUMENTATION SHALL BE
 SUBMITTED, REVIEWED, AND APPROVED PRIOR TO ISSUING THE
 PERMIT.