| 2019-07-09 11:56:53 | 3RD REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1) THE PLUMBING PAGES CLEARLY SHOW NEW SANITARY AND |
| | WATER PIPING TO THE WATER FOUNTAIN LOCATION. PLEASE |
| | PROVIDE EXITING DEMO PLAN. I LOOKED INTO OUR RECORDS |
| | FOR THAT BUILDING AND COULD NOT FIND ANY SHOWING A |
| | WATER FOUNTAIN IN THAT LOCATION. AFTER DISCUSSING IT |
| | WITH THE BUILDING OFFICIAL WE FEEL THAT THIS DOES NOT |
| | FALL UNDER THE EXCEPTION AS BEING TECHNICALLY |
| | INFEASIBLE. |
| | |
| | 2) ROBERT BROWN ASK IF THIS WORK WAS COMPLYING WITH FBC |
| | ACC 202.4, 202.4.1, 202.4.2 PLEASE PROVIDE A COST BREAK |
| | DOWN TO SHOW THAT A MIN OF 20% OF THE TOTAL COST OF THE |
| | JOB IS BEING USED TO PROVIDE 1.AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA, 2. ACCESSIBLE REST ROOMS, |
| | TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED |
| | AREA IN THAT ORDER. PER FBC ACC 202.4.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |