| 2019-06-27 11:36:22 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS. |
| | |
| | 1. TWO WATER FOUNTAINS ARE REQUIRED THEY SHALL COMPLY |
| | WITH FBC PL [BE] 410.3 PROVIDE HIGH AND LOW DRINKING |
| | FOUNTAINS. WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT |
| | FEWER THEN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| | FOR STANDING PERSONS. |
| | FBC ACC 211.2 MINIMUM NUMBER.NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.1 THEOUGH 602.6 AND ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.7. |
| | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT |
| | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS |
| | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | IN THE RESPONSE LETTER THE ARCHITECT IS CLAIMING THE |
| | EXCEPTION #2 FBC ACC 202.3 A SIGNED AND SEALED LETTER |
| | ON THE ARCHITECTS LETTER HEAD EXPLAINING HOW IT MEETS |
| | THE EXCEPTION SHALL BE SUBMITTED AND SHALL BE APPROVED |
| | BY THE BUILDING OFFICIAL ROBERT BROWN BEFORE PERMIT CAN |
| | BE APPROVED. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT A0.05 PLEASE REMOVE DETAILS FOR THE PLUMBING |
| | FIXTURES THA ARE NOT IN THE SCOPE OF WORK. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. A0.05 THE DETAIL FOR THE WATER FOUNTAIN SHOWS A |
| | PARALLEL CLEAR FLOOR SPACE THR CODE REQUIRES A FRONTAL |
| | APPROACH PLEASE CLARIFY. FBC ACC 602.2 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| 2019-06-26 12:14:26 | GPJ TO DO REVIEW. |