| Plan Review Notes For Permit 19050525 |
| Permit Number |
19050525 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-27 10:10:49 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | 1. A SEPERATE PERMIT IS REQUIRED FOR THE 9TH FLOOR. | | | APPROVED WITH PROVISO. CONTRACTOR TO APPLY; APPLICATION | | | IN PROGRESS. | | | | | | 2. REVISE PLAN TO SHOW HOW THE ELEVATOR LOBBY SHOWN | | | COMPLIES WITH FBC B 3006.3. | | | APPROVED WITH PROVISO. ADJUST WALL ADJACENT TO LOBBY | | | DOOR TO COMPLY WITH ACCESSIBILE MANEUVERABILITY(WALL | | | NEEDS TO HAVE AN 18" HORIZONTAL MEASUREMENT). | | | | | | 3. PAGE A0.03 THE COMMON PATH OF TRAVEL IS NOT CLEAR. | | | PROVIDE INFORMATION ON HOW THE COMMON PATH OF TRAVEL IS | | | AT 68'. | | | FAIL. | | | | | | 4. APPROVED | | | | | | 5. APPROVED | | | | | | 6. APPROVED | | | | | | 7. APPROVED |
|