Plan Review Notes
Plan Review Notes For Permit 19050525
Permit Number 19050525
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-05-20 15:24:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.11 - THERE IS A DOUBLE DOOR INDICATED AT
 THE MECHANICAL ROOM WITHIN A RATED WALL; HOWEVER, THERE
 IS NO INDICATION ON THE DOOR SCHEDULE THAT THESE DOORS
 HAVE FIRE RATING OR SELFCLOSING.
  
 PLEASE REVIEW AND COORECT OR JUSTIFY.
  
  
  
 2) SHEET A 1.12 - THERE IS A DOUBLE DOOR INDICATED AT
 THE MECHANICAL ROOM WITHIN A RATED WALL; HOWEVER, THERE
 IS NO INDICATION ON THE DOOR SCHEDULE THAT THESE DOORS
 HAVE FIRE RATING OR SELFCLOSING.
  
 PLEASE REVIEW AND COORECT OR JUSTIFY.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  