Plan Review Notes
Plan Review Notes For Permit 19050525
Permit Number 19050525
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-05 09:15:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A SEPARATE PERMIT IS REQUIRED FOR THE 9TH FLOOR.
 CONTACT ME AFTER ALL REVIEWS HAVE PASSED TO COORDINATE.
  
 2. REVISE PLAN TO SHOW HOW THE "ELEVATOR LOBBY" SHOWN
 COMPLIES WITH FBC B 3006.3. IF THE ELEVATORS ARE
 PRESSURIZED, PLEASE ADVISE VIA EMAIL PRIOR TO
 RESUBMITTING.
  
 3. A0.03, COMMON PATH OF TRAVEL NOT CLEAR. OCCUPANCY
 ANALYSIS STATES THAT THIS IS 68', BUT IT APPEARS THAT
 IT IS 140'. SEE FBC CHAPTER 2, DEFINITION OF COMMON
 PATH.
  
 4. A0.03, ROOM 806, TAC WORKSTATION ADA, REVISE PLAN TO
 SHOW COMPLIANCE, FBC A 904. NO DIMENSIONS FOR THE
 ACCESSIBLE ROUTE INTO AND OUT OF THE SPACE WERE
 PROVIDED; PROVIDE DIMENSIONS AND DETAIL FOR THE SERVICE
 COUNTER.
  
 5. REVISE PLAN TO CLARIFY AREAS WHICH WOULD BE REQUIRED
 TO COMPLY WITH FBC A 808 (A0.03 SHOWS A "GRAND JURY").
  
 6. A0.02 ROOM 806 SHOWS "SELF HELP" STATIONS. PROVIDE A
 DETAIL, FBC A 904.
  
 7. SEE FIRE COMMENTS REGARDING MECHANICAL ROOM RATING;
 CHECK ALL.
  
  
  