| 2019-05-20 11:17:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19050491 |
| | 5/20/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: THE ORIGINAL KITCHEN HOOD PLANS SUBMITTED |
| | UNDER PERMIT #19011174 MUST BE REVISED TO SHOW THE |
| | CHANGES TO THE GREASE EXHAUST DUCT RUN AND NEW KEF |
| | LOCATION, HOWEVER PLEASE NOTE THE PROPOSED NEW PLANS |
| | ARE DEFICIENT- SEE COMMENTS BELOW. |
| | |
| | 2) M1: PROVIDE EITHER A FIRE-RATED SHAFT FOR THE GREASE |
| | EXHAUST DUCT PENETRATING THE FIRE-RATED CEILING OR A |
| | FIRE WRAP ENCLOSURE- SEE SECTIONS 506.3.11, 506.3.11.1, |
| | 506.3.11.2, AND 506.3.11.3 FBC M |
| | |
| | 3) M1: THE GREASE DUCT SHALL EITHER SLOPE TO THE HOOD |
| | OR TO A GREASE RESERVOIR IN ACCORDANCE WITH SECTION |
| | 506.3.7 FBC M. NO RESERVOIR IS SHOWN ON THE PLAN. |
| | |
| | 4) M1: THE GREASE EXHAUST TERMINATION SHALL BE 10' |
| | ABOVE GRADE- SECTION 506.3.13.3 FBC M |
| | |
| | 5) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION |
| | OF THE GREASE EXHAUST FAN AND CURB- SECTION 301.15 FBC |
| | M. |
| | |
| | 6) SHEET ID-3.0 INDICATES A CHASE DOWN THE SIDE OF THE |
| | BUILDING TO ENCLOSE THE EXHAUST DUCT HOWEVER NO |
| | CONSTRUCTION DETAILS HAVE BEEN PROVIDED- SECTION |
| | 107.2.1 WPB, AND SECTION 506.3.11.1 FBC M. PLEASE NOTE |
| | THAT ACCESS TO CLEANOUTS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 506.3.8 FBC M. |
| | |
| | 7) ID-3.0: THERE IS A NOTE REFERENCING A SOUTHWEST |
| | ELEVATION DETAIL, HOWEVER THE ELEVATION HAS NOT BEEN |
| | PROVIDED- SECTION 107.2.1 WPB |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |