| Plan Review Notes For Permit 19050455 |
| Permit Number |
19050455 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-28 10:36:30 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) 200 AMPERE TRANSFER SWITCH FEEDING 2 PANELS ONE 60A | | | AND ONE 100A ? OVERCURRENT DEVICE TO LARGE FOR THE | | | WIRE. | | | E3602.1AMPACITY OF UNGROUNDED CONDUCTORS. | | | UNGROUNDED SERVICE CONDUCTORS SHALL HAVE AN AMPACITY OF | | | NOT LESS THAN THE LOAD SERVED. 200A BREAKER FEEDING 60 | | | AND 100 AMPERE LOADS. | | | | | | 2) FEEDERS AND SERVICE MIXED IN SAME ENCLOURE (GUTTER) | | | E3601.4OTHER CONDUCTORS IN RACEWAY OR CABLE. | | | CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE | | | INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE CABLE. | | | (230.7) | | | | | | 3) COTTAGE DOES NOT SHOW GROUNDING PER 250.32 | | | E3607.3BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR | | | BRANCH CIRCUIT(S). | | | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH | | | CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) | | | SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION | | | E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS | | | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING | | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN SECTION E3608 SHALL BE INSTALLED. | | | [250.32(A)] |
|