| Plan Review Notes For Permit 19050443 |
| Permit Number |
19050443 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-21 07:20:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SHEET A-121, PLANS ARE NOT DIGITALLY SIGNED, NO | | | REVISION SHOWN (NO CLOUDS, NO REVISION DATE AND | | | NUMBER), PLAN SIGNED 8/14/18. NARRATIVE INDICATES THAT | | | THERE ARE REVISIONS TO THIS PAGE. | | | | | | 2. SHEET S-201 IS NOT DIGITALLY SIGNED (BUT APPEARS | | | CODE COMPLIANT). PLEASE PROVIDE A DIGITALLY SIGNED PAGE | | | WHICH INCLUDES EITHER THE IMAGE OF THE ENGINEER'S SEAL | | | OR A DIGITAL SIGNATURE THAT STATES THAT THE PLAN IS | | | "SIGNED AND SEALED". ALSO REVISE THE PLAN OR DIGITAL | | | SIGNATURE TO INCLUDE THE LANGUAGE REQUIRED BY | | | FAC61G15-23.002 (REGARDING PRINTED COPIES OF THE PLAN). | | | | | | PLEASE RESUBMIT WITH DIGITALLY SIGNED PLANS, FS471, | | | FS481 TO RESOLVE. | | | | | | | | | |
|