| 2019-08-03 14:22:46 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | 1. OK | | | 2. PROVIDE MORE INFORMATION ABOUT THE SHED: | | | A. OK | | | B. OK | | | C. PROVIDE MORE INFORMATION: | | | 1.) 4" COLUMN TO BOTTOM FLANGE OF W6X8.5 BEAMS? | | | 2.) LOCATION OF WELDS AT BEAM TO JOIST CONNECTIONS? | | | 3.) BRACING/BRIDGING REQUIRED | | | DETAILS/LOCATIONS/CONNECTIONS? | | | 4.) WELDING PROCESS (SMAW/GMAW)? | | | 5.) WELDING FILLER METALS (E 7018)? | | | 6.) METAL DECKING ATTACHMENT DETAILS APPEAR TO SHOW LAP | | | CONNECTIONS ONLY. MISSING DECKING TO JOIST CONNECTION | | | DETAILS? | | | D. ROOFING INFORMATION IS MISSING? | | | E. ARE THERE GOING TO BE ANY WALLS/WINDOWS/DOORS? | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|