 1. PER FBC PL 912.1 AND 912.2, THE SHOWER DRAINS IN
 BATHS 2 AND 3 SHALL CONNECT INDEPENDENTLY TO THE WET
 VENT. THE SHOWER DRAINS SHALL NOT CONNECT TO THE TO THE
 WATER CLOSET AHEAD OF THE VENT.SEE REDLINED COMMENTS ON
 PLAN SHEET E101.
  