Date Text
2019-05-13 18:02:381ST REVIEW: 19050400
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. E101 THE LAUNDRY RISER IS SHOWING A HORIZONTAL
 DRY VENT THE MASTER BATHROOM IS SHOWING A HORIZONTAL
 DRY VENT ON THE TOILET, A VENT SHALL RISE VERTICAL
 ABOVE THE CENTERLINE OF THE PIPE TO ABOVE THE FLOOD
 LEVEL RIM OF THE FIXTURE. PER FBC PL 905.3, 905.4
  
 2. PLEASE PROVIDE A EXISTING FLOOR PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
  