| 2019-05-13 11:31:58 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M101: THE DRYER AND KITCHEN HOOD EXHAUST DUCTS |
| | SHALL BE INDEPENDENT OF OTHER EXHAUST SYSTEMS- SECTIONS |
| | 504.1 AND 505.3 (12) FBC M. THE PLANS SHOW THE DUCTS |
| | DISCHARGING INTO THE SAME CHASAES AS THE TOILET EXHAUST |
| | DUCTS. |
| | |
| | 2) SUBMIT MANUIFACTURER'S SPECIFICATIONS FOR THE |
| | KITCHEN HOOD AND EXHAUST DUCT- SECTION 505.1 FBC M. SEE |
| | SECTION 505.2 FOR MAKEUP AIR REQUIREMENTS. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | RANGE AND OVEN.- SECTION 917.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |