| Plan Review Notes For Permit 19050400 |
| Permit Number |
19050400 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-14 14:44:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET A 102 - THERE ARE NO INDICATIONS OF WHAT IS | | | EXISTING AND WHAT BEING REVISED. | | | | | | PER NFPA 101 | | | | | | PER NFPA 1 | | | 1.14 PLAN REVIEW. | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE | | | REVISIONS OR MODIFICATIONS ARE FROM THE EXISTING. | | | | | | | | | | | | 2) SHEET E 101- THERE ARE NO INDICATIONS OF ANY | | | EXISTING FIRE ALARM DEVICES AND/OR SMOKE ALARMS OR | | | PROPOSED LOCATIONS. | | | | | | PLEASE PROVIDE ALL EXISTINE FIRE ALARM AND SD DEVICES | | | AND ANY PROPOSED LOCATIONS COMPLIANT WITH NFPA 101. | | | | | | | | | | | | 3) ALL WORK ON THE FIRE ALARM SYSTEM/DEVICES/EQUIPMENT | | | SHALL BE DONE BY CERTIFIED FA CONTRACTORS UNDER | | | SEPARATE SHOP DRAWINGS. | | | | | | PLEASE P[ROVIDE AN APPLICABLE NOTE. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|