2019-09-14 11:13:37ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW - DISREGARD PREVIOUS 4TH REVIEW LOCKED OUT
 OF COMMUNITY PLUS
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. CORRECTED
  
 2. CORRECTED
  
 3. ELEVATION CERTIFICATES ARE REQUIRED. SEE COMMENTS
 UNDER NFIP REVIEW. (INCOMPLETE)
  
 4. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND
 EXTERIOR DOORS. (NOT ADDRESSED - LIST PRODUCT APPROVALS
 ON WINDOW AND DOOR SCHEDULE OR DESIGNER SHALL REVIEW
 AND APPROVE EACH PRODUCT APPROVAL OR PRODUCT APPROVALS
 MAY BE DEFERRED BY PLACING STATEMENT ON PLAN "PRODUCT
 APPROVALS ARE DEFERRED")
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
 OPTION:
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. PROVIDE SOILS REPORT. (TWO ENGINEER'S SIGNED SOILS
 REPORT, NEITHER SIGNATURE AND SEAL IS VALID. PROVIDE
 HARD COPY OF SOILS REPORT WITH ORIGINAL SIGNATURES AND
 SEALS AT TIME OF PERMIT PICK-UP)
  
 6. PALM BEACH COUNTY IMPACT FEES (CLOSED - SEE IMPACT
 FEE REVIEW)
  
 7. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED) (SUBMITTAL SHALL BE SIGNED BY PREPERARE
 AND OWNER/AGENT)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 8. PROVIDE FLOOD VENTS IN GARAGE WALLS. (NOT ADDRESSED)
 (PRODUCT APPROVALS PROVIDED FOR TWO DIFFERENT SMART
 VENTS, NO VENTS LOCATED ON FOUNDATION PLAN. PRODUCT
 APPROVALS SHALL BE REVIEWEED AND APPROVED BY DESIGNER)
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.6.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE
 24.
  
 ADVISORY:
  
 4X FEES
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  