| Date |
Text |
| 2019-09-07 08:50:22 | ADDRESS: 110 FLAGLER LANE PERMIT # 19050386 |
| | TYPE: BLD-RES NEW SFR |
| | |
| | MECHANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW |
| | HAVE BEEN NOTED CORRECTED. |
| | |
| | THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST |
| | REVIEW (NOT ADDRESSED) IN PARANTHESIS. |
| | |
| | ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS. |
| | |
| | 1. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL. |
| | (NOT ADDRESSED) (ELEVATION CERTIFICATE UNSUCESSFULLY |
| | UPLOADED, NO INFORMATION AVAILABLE) |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | 2. EXTERIOR MECHANICAL EQUIPMENT SHALL BE INSTALLED AT |
| | OR ABOVE THE DESIGN FLOOD ELEVATION. (DFE) (NOT |
| | ADDRESSED - ELEVATION OF EQUIPMENT ON ELEVATION |
| | CERTIFICATE IS BELOW DESIGN FLOOD ELEVATION) (ELEVATION |
| | CERTIFICATE UNSUCESSFULLY UPLOADED, NO INFORMATION |
| | AVAILABLE) |
| | |
| | 3. CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN |
| | FLOOD ELEVATION (DFE). (ELEVATION CERTIFICATE |
| | UNSUCESSFULLY UPLOADED, NO INFORMATION AVAILABLE) |
| | FBC R M1401.5 AND FBC R 322.1.6 |
| | M1401.5 FLOOD HAZARD. |
| | IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE |
| | R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES |
| | SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH |
| | SECTION R322.1.6. |
| | R322.1.6 PROTECTION OF MECHANICAL, PLUMBING AND |
| | ELECTRICAL SYSTEMS. |
| | |
| | 4. PROVIDE MANUFACTURERS SPECIFICATIONS FOR EXHAUST |
| | HOOD. PROVIDE EXHAUST RATE IN CUBIC FEET PER MINUTE. |
| | (NOT ADDRESSED) (NOT PROVIDED) |
| | G2408.1 (305.1)GENERAL. FBC SEC. 107.2.1. |
| | EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED |
| | BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE |
| | CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS |
| | AND THIS CODE. |
| | |
| | 5. PROVIDE MAKE UP AIR CALCULATIONS. (NOT ADDRESSED) |
| | (NOT PROVIDED) |
| | M1503.4 MAKEUP AIR REQUIRED. |
| | EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF |
| | 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE |
| | MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A |
| | RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. SUCH |
| | MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH NOT LESS THAN |
| | ONE DAMPER. EACH DAMPER SHALL BE A GRAVITY DAMPER OR AN |
| | ELECTRICALLY OPERATED DAMPER THAT AUTOMATICALLY OPENS |
| | WHEN THE EXHAUST SYSTEM OPERATES. DAMPERS SHALL BE |
| | ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND |
| | REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION OR |
| | ANY OTHER DUCTS NOT CONNECTED TO THE DAMPER BEING |
| | INSPECTED, SERVICED, REPAIRED OR REPLACED. |
| | EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS |
| | NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF |
| | EXHAUSTING: |
| | 1. (A)FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR |
| | 2. (B)MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE |
| | THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY |
| | VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF |
| | THE STRUCTURE. |
| | |
| | 6. NOTE ON PLAN PAGE M-1 REFERENCES DETAIL D/S-4 FOR |
| | SECTION VIEW OF MSU#1 & FCU#1. THERE IS NO DETAIL ON |
| | PAGE S-4. PLEASE CLARIFY. CORRECTED |
| | |
| | 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR |
| | FIREPLACE. (NOT ADDRESSED) (NOT PROVIDED) |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR CU |
| | TIE DOWN. (NOT ADDRESSED) (NOT PROVIDED) |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. PROVIDE CFM RATING FOR BATHROOM EXHAUST FANS. |
| | CORRECTED |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | NEW COMMENTS: |
| | |
| | 10. PROVIDE SHOP DRAWINGS FOR KITCHEN EXHAUST HOOD. |
| | (NOT PROVIDED) |
| | |
| | 11. PROVIDE MAKE UP AIR CALCULATIONS FOR KITCHEN |
| | EXHAUST HOOD. (NOT PROVIDED) |
| | |
| | 12. NOTE ON PLAN PAGE M-1 STATES OWNER MAY SUBSTITUTE |
| | EQUIPMENT. ANY CHANGES FROM APPORVED PLANS WILL REQUIRE |
| | A REVISION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |