| 2019-08-05 15:25:46 | ADDRESS: 110 FLAGLER LANE PERMIT # 19050386 |
| | TYPE: BLD-RES NEW SFR |
| | |
| | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW |
| | HAVE BEEN NOTED CORRECTED. |
| | |
| | THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST |
| | REVIEW (NOT ADDRESSED) IN PARANTHESIS. |
| | |
| | ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS. |
| | |
| | |
| | 1. AIC RATING OF SERVICE DISCONNECT AND PANEL (PER |
| | PROVISO ON PLAN) |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | |
| | 2. PROVIDE LOAD CALCULATIONS BASED ON FBC R TABLE |
| | 3602.2. CORRECTED |
| | |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (SEE |
| | NOTE ON PLAN) |
| | |
| | 4. EMERGENCY GENERATOR AND TRANSFER SWITCH WILL BE BY |
| | SEPERATE PERMIT. N/A |
| | |
| | 5. REMOVE #4 GROUNDING CONDUTOR BETWEEN METER AND |
| | DISCONNECT. CORRECTED |
| | |
| | 6. NOTE A ON ELECTRICAL NOTES REFERENCING ARC-FAULT |
| | PROTECTION SHALL INCLUDE KITCHENS. CORRECTED |
| | |
| | 7. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| | SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT |
| | OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1. CORRECTED |
| | |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D); FBC RE E3902.10. CORRECTED |
| | |
| | 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE E3901.2.1. CORRECTED |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |