Plan Review Notes
Plan Review Notes For Permit 19050386
Permit Number 19050386
Review Stop E
Sequence Number 2
Notes
Date Text
2019-08-05 15:25:46ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
  
 1. AIC RATING OF SERVICE DISCONNECT AND PANEL (PER
 PROVISO ON PLAN)
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
  
 2. PROVIDE LOAD CALCULATIONS BASED ON FBC R TABLE
 3602.2. CORRECTED
  
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (SEE
 NOTE ON PLAN)
  
 4. EMERGENCY GENERATOR AND TRANSFER SWITCH WILL BE BY
 SEPERATE PERMIT. N/A
  
 5. REMOVE #4 GROUNDING CONDUTOR BETWEEN METER AND
 DISCONNECT. CORRECTED
  
 6. NOTE A ON ELECTRICAL NOTES REFERENCING ARC-FAULT
 PROTECTION SHALL INCLUDE KITCHENS. CORRECTED
  
 7. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1. CORRECTED
  
 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10. CORRECTED
  
 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1. CORRECTED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  