2019-06-06 10:11:41ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY). SIGNED BY BUILDER.
  
 2. EXTERIOR MECHANICAL EQUIPMENT SHALL BE INSTALLED AT
 OR ABOVE THE DESIGN FLOOD ELEVATION. (DFE)
 CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE).
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
 R322.1.6 PROTECTION OF MECHANICAL, PLUMBING AND
 ELECTRICAL SYSTEMS.
  
 4. PROVIDE MANUFACTURERS SPECIFICATIONS FOR EXHAUST
 HOOD. PROVIDE EXHAUST RATE IN CUBIC FEET PER MINUTE.
 G2408.1 (305.1)GENERAL. FBC SEC. 107.2.1.
 EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED
 BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE
 CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS
 AND THIS CODE.
  
 5. PROVIDE MAKE UP AIR CALCULATIONS.
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE
 MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A
 RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. SUCH
 MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH NOT LESS THAN
 ONE DAMPER. EACH DAMPER SHALL BE A GRAVITY DAMPER OR AN
 ELECTRICALLY OPERATED DAMPER THAT AUTOMATICALLY OPENS
 WHEN THE EXHAUST SYSTEM OPERATES. DAMPERS SHALL BE
 ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND
 REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION OR
 ANY OTHER DUCTS NOT CONNECTED TO THE DAMPER BEING
 INSPECTED, SERVICED, REPAIRED OR REPLACED.
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 1. (A)FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 2. (B)MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 6. NOTE ON PLAN PAGE M-1 REFERENCES DETAIL D/S-4 FOR
 SECTION VIEW OF MSU#1 & FCU#1. THERE IS NO DETAIL ON
 PAGE S-4. PLEASE CLARIFY.
  
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 FIREPLACE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR CU
 TIE DOWN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. PROVIDE CFM RATING FOR BATHROOM EXHAUST FANS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  