| 2019-06-06 13:42:56 | ADDRESS: 110 FLAGLER LANE PERMIT # 19050386 |
| | TYPE: BLD-RES NEW SFR |
| | |
| | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1. AIC RATING OF SERVICE DISCONNECT AND PANEL |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| | FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| | NOT LESS THAN 10,000 AMPERES. (110.9) |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| | |
| | 2. PROVIDE LOAD CALCULATIONS BASED ON FBC R TABLE |
| | 3602.2. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2. |
| | 2A. REMOVE CALCULATION FOR CONVIENCE LIGHTING. |
| | 2B. GENERAL LIGHTING LOAD WILL BE CALCULATED BY |
| | MULTIPLYING THE SQUARE FOOTAGE BY 3 VA. |
| | 2C. HVAC DOES NOT REQUIRE A DF OF 1.25. |
| | |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | 4. EMERGENCY GENERATOR AND TRANSFER SWITCH WILL BE BY |
| | SEPERATE PERMIT. |
| | |
| | 5. REMOVE #4 GROUNDING CONDUTOR BETWEEN METER AND |
| | DISCONNECT. |
| | THE # 4 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE |
| | INCLUDED IN THE CONDUIT FROM FPL TO THE METER OR IN THE |
| | CONDUIT FROM THE METER TO THE MAIN DISCONNECT SWITCH. |
| | PROVIDE CORRECTION. NEC 250.6; FBC RE E3610.4. |
| | |
| | 6. NOTE A ON ELECTRICAL NOTES REFERENCING ARC-FAULT |
| | PROTECTION SHALL INCLUDE KITCHENS. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC |
| | 210.12; FBC RE E3902.16. |
| | |
| | 7. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| | SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT |
| | OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1. |
| | |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D); FBC RE E3902.10. |
| | |
| | 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE E3901.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |