| Plan Review Notes For Permit 19050361 |
| Permit Number |
19050361 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-19 12:55:54 | 1) THE NEW SHOWER IN BATH #2 SHALL BE A MINIMUM OF 30 | | | INCHES IN WIDTH PER 2017 FBC-RES. SEC. P2708.1. | | | 2) SHOW THE PLUMBING FIXTURES FROM BATHROOM #1 ON THE | | | SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE SHUTOFF VALVES FOR THE WASHING MACHINE SHALL BE | | | ACCESSIBLE. SHOW WHERE THESE VALVES WILL BE LOCATED. | | | 2017 FBC-RES. SEC. P2903.9.3. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|