| 2019-05-08 16:38:54 | GAS 1ST REVIEW**DENIED** | | | | | | 1) CITY RECORDS ( PERMIT # 04081048 SHOW OTHER GAS | | | EQUIPMENT (DRYER) .LIST THE BTU LOAD OF EACH APPLIANCE | | | AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 | | | FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 ) | | | THROUGH G2413.4 (21). | | | | | | 2) PERMIT APPLICATION CALLS OUT RANGE BUT NO RANGE SHOW | | | ON GAS PLAN OR ISOMETRIC. LIST THE BTU LOAD OF EACH | | | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER | | | TO THE 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | | | | 3) PROVIDE INSTALLATION MANUAL FOR NEW TANKLESS WATER | | | HEATER. FBC 107.2.1 | | | | | | 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE | | | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION | | | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN | | | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER | | | HEATER SHALL COMPLY WITH THE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND | | | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | 5) A PLUMBING AND ELECTRICAL PERMIT IS REQUIRED FOR THE | | | INSTALLATION OF A TANKLESS WATER HEATER, NO OTHER | | | APPLICATIONS HAVE BEEN SUBMITTED. FBC 105.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | |
|