| 2019-06-17 14:32:08 | PLUMBING 2ND REVIEW**DENIED**FL ST 553.80 (B)2BWITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) 2ND REQUEST.A GAS TANKLESS WATER HEATER IS CALLED |
| | OUT ON THE R405-2017 FORM LISTED @ .80 E.F. THE FEDERAL |
| | MIN EFFICIENCY AS OF 12/29/2016 IS .82%. REFER TO |
| | FEDERAL REGISTER VOL. 81, NO. 250. YOU MUST SUBMIT A |
| | CORRECTED R405-2017 FORM WITH THE CORRECT E.F. ALSO IT |
| | IS STILL UNCLEAR IF THE WATER HEATER IS GAS OR ELC |
| | TANKLESS. PLEASE CLARIFY. |
| | |
| | 2) ANSWERED |
| | |
| | 3) ANSWERED |
| | |
| | 4) 2ND REQUEST. ISOMETRIC DRAWING ON SHT. E1.0 MASTER |
| | BATHROOM SHOW 2 FIXTURES BEYOND THE ACTUAL VENT. ONLY |
| | ONE IS PERMITTED IN A WET VENT SYSTEM. FBC-R P3108.2.1 |
| | AND THE FOYER BATH SHALL HAVE EACH WET-VENTED FIXTURE |
| | CONNECT TO THE HORIZONTALLY BRANCH IS PART OF THE WET |
| | VENT. FBC-R P3108.1 |
| | |
| | 5) 2ND REQUEST* NOT FULLY ADDRESSED. SHT. E1.0 PANEL |
| | SCHEDULE SHOWS1 DOUBLE 50 AMP BREAKER FOR THE TANKLESS. |
| | THE MAX WATER HEATER BASED ON BREAKER WOULD BE A MAX |
| | 11KW. THIS WOULD BE UNDERSIZED FOR THIS HOME. FBC |
| | 107.3.5 |
| | |
| | 6) 2ND REQUEST.PROVIDE COMPLETE INSTALLATION MANUAL FOR |
| | TANKLESS WATER HEATER TO INCLUDE HEAT RISE CHARTS. FBC |
| | 107.2.1. THE WATER HEATER TYPE, SIZE AND INSTALLATION |
| | MANUAL SHALL BE SUBMITTED FOR PLAN REVIEW DUE TO THE |
| | FACT THAT TANKLESS WATER HEATER'S OPERATE BASE ON HEAT |
| | RISE OF THE INCLOMING WATER SO WE NEED TO VERIFY THE |
| | UNIT IS PROPERLY SIZED FOR THE HOME. |
| | |
| | 7) ANSWERED. |
| | |
| | 8) 2ND REQUEST. IN THE PLUMBING NOTES #14 YOU CALL YOU |
| | FOR A HOT WATER RETURN SYSTEM. PLEASE ADD NOTE ALL HOT |
| | WATER PIPING INSULATED TO A MIN R-3. FBC-ENERGY |
| | 403.5.3.. UNABLE TO LOCATE YOUR REVISED NOTED. |
| | |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |