| 2019-06-18 15:27:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THERE IS A CONFLICT BETWEEN THE RISER DIAGRAM AND |
| | THE PANEL SCHEDULES. IS PANEL B FED FROM PANEL A, OR IS |
| | IT FED FROM PANEL B DISCONNECT? WHERE IS PANEL B |
| | DISCONNECT FED FROM? THERE IS CONFLICT ALSO WITH WIRE |
| | SIZE WITH PANEL A STATING THAT PANEL B IS FED WITH 6 |
| | GAUGE WIRE AND THE RISER STATING THAT IT IS FED WITH 1 |
| | GAUGE WIRE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS |
| | AS NEEDED. NEC 215.5; WPB FBC 107.2.1 |
| | 2. PROVIDE LOAD CALCULATION FOR PANEL B. IF THIS PANEL |
| | IS FED WITH LESS THAN A 100 AMP FEEDER, DEMAND FACTORS |
| | ARE NOT PERMITTED TO BE USED. NEC 220; FBC RE E3602.2 |
| | OR E3701.2 AS APPLICABLE. |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 4. PROVIDE GFCI PROTECTION FOR GAS WATER HEATER IGNITOR |
| | RECEPTACLE. NEC 210.8; FBC RE E3902.3 |
| | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 7. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| | 801.2, OR 901.2 AS APPLICABLE. |
| | 8. THERE ARE TWO SHEETS NAMED E1.0. THE SECOND ONE HAS |
| | THE PLUMBING RISER ON IT. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 9. THE CONDUIT FROM METER CAN TO MAIN SERVICE |
| | DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT GROUNDING |
| | CONDUCTOR. PROVIDE CORRECTION. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |