| 2019-05-15 13:08:58 | PLUMBING 1ST REVISION REVIEW**DENIED** |
| | |
| | 1) A GAS TANKLESS WATER HEATER IS CALLED OUT ON THE |
| | R405-2017 FORM LISTED @ .80 E.F. THE FEDERAL MIN |
| | EFFICIENCY AS OF 12/29/2016 IS .82%. REFER TO FEDERAL |
| | REGISTER VOL. 81, NO. 250. |
| | |
| | 2) PROVIDE LOCATION OF THE ACCESSIBLE SHUT OFF VALVES |
| | FOR THE STACKABLE WASHING AND DRYER. FBC-R P2903.9.3 |
| | |
| | 3)PROVIDE NOTE THAT FREE STANDING TUB VALVE SHALL BE |
| | TEMPERED BY AN ASSE 1070 DEVICE PER FBC-R P 2713.3 OR |
| | MEET ONE OF THE REQUIREMENTS IN P2708.4 |
| | |
| | 4) ISOMETRIC DRAWING ON SHT. E1.0 MASTER BATHROOM SHOW |
| | 2 FIXTURES BEYOND THE ACTUAL VENT. ONLY ONE IS |
| | PERMITTED IN A WET VENT SYSTEM. FBC-R P3108.2.1 AND THE |
| | FOYER BATH SHALL HAVE EACH WET-VENTED FIXTURE CONNECT |
| | TO THE HORIZONTALLY BRANCH IS PART OF THE WET VENT. |
| | FBC-R P3108.1 |
| | |
| | 5) SHT. E1.0 PANEL SCHEDULE CALLS OUT ELC TANKLESS |
| | 4.5KW WHILE THE R405-2017 FORM CALLS OUT GAS TANKLESS. |
| | PLEASE CLARIFY AND PROVIDE LOCATION PLAN OF TANKLESS |
| | WATER HEATER. FBC 107.3.5 |
| | |
| | 6) PROVIDE COMPLETE INSTALLATION MANUAL FOR TANKLESS |
| | WATER HEATER TO INCLUDE HEAT RISE CHARTS. FBC 107.2.1 |
| | |
| | 7) PROVIDE SHOWER PAN DETAIL TO SHOW PRE-PITCH AS |
| | REQUIRED IN FBC-R P 2709.3 |
| | |
| | 8) IN THE PLUMBING NOTES #14 YOU CALL YOU FOR A HOT |
| | WATER RETURN SYSTEM. PLEASE ADD NOTE ALL HOT WATER |
| | PIPING OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED |
| | TO A MIN R-3. FBC-ENERGY 403.5.3. |
| | |
| | |
| | |
| | |