Plan Review Notes
Plan Review Notes For Permit 19050351
Permit Number 19050351
Review Stop E
Sequence Number 2
Notes
Date Text
2019-05-24 14:05:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE IS A CONFLICT WITH RISER DIAGRAM AND PANEL
 SCHEDULES. WHAT APPEARS TO BE A SUB-PANEL IS SHOWN AS
 100 AMP, 150 AMP, AND 200 AMP. WHICH IS IT? IS THIS
 PANEL NEW OR EXISTING, IT IS MARKED BOTH NEW AND
 EXISTING WHICH IS IMPOSSIBLE? WHAT WIRE SIZE IS TO BE
 INSTALLED FOR THIS PANEL. WHERE IS THIS FED FROM? IT
 SHOWS BEING CONNECTED TO THE MAIN PANEL, BUT THERE IS
 NO BREAKER IN THE MAIN PANEL FOR THIS. PROVIDE ACCURATE
 RISER DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30;
 FBC RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. PLAN SHOWS A TANKLESS WATER HEATER, BUT THE
 CALCULATION INCLUDES A STANDARD WATER HEATER. LOAD
 CALCULATION SHOULD BE IN THE FORMAT STIPULATED IN THE
 FBC RESIDENTIAL. THERE SHOULD BE AN OVERALL LOAD
 CALCULATION FOR THE SERVICE, AS WELL AS THE CALCULATION
 FOR ANY SUB-PANEL. NEC 220; FBC RE E3602.2
 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  