| Plan Review Notes For Permit 19050351 |
| Permit Number |
19050351 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-22 17:30:49 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1ST BUILDING PLAN REVIEW DENIED: | | | | | | FBC B 107. | | | | | | 1. PROVIDE A WINDOW/DOOR SCHEDULE, ON PLANS, FOR | | | WINDOWS AND DOORS. THE PLANS ARE NOT CLEAR AS TO WHAT | | | EACH INDICATOR REPRESENTS (A, B, 1, 3, 4 ?). | | | | | | 2. PRODUCT APPROVAL # 17-0504.01 (IMPACT RESISTANT | | | ALUMINUM OUTSWING FRENCH DOOR) WAS SUBMITTED BUT THERE | | | IS NO INDICATED LOCATION ON | | | PLANS FOR THIS DOOR. | | | | | | 3. PROVIDE DETAILS FOR THE INTERIOR WALL FRAMING, | | | DRYWALL, AND CEMENT TYPE WALL BOARD FOR THE NEW SHOWER | | | AREAS. PLEASE INCLUDE INSULATION (IF DESIRED), | | | ANCHORING, AND FASTENING TYPES/PATTERNS. | | | | | | NOTE: | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|