Plan Review Notes
Plan Review Notes For Permit 19050329
Permit Number 19050329
Review Stop THRESHOLD
Sequence Number 1
Notes
Date Text
2019-05-15 12:12:50THRESHOLD PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. TEMPORARY MEMBRANE STRUCTURES (TENTS)
 2017 FBC CHAPTER 31
 SPECIAL CONSTRUCTION
  
 SECTION 3103
 TEMPORARY STRUCTURES
  
 2. CONFORMANCE PER SECTION 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR
 STRUCTURES WITH SPANS OF 30 FEET OR GREATER.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701 FOR EACH TENT
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED.
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
  A) STATE OCCUPANT LOAD.
  B) IDENTIFY MEANS OF EGRESS.
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT.
  D) PROVIDE FLOOR LAYOUT OF EVENT.
  D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN
  E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
  F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203
  G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES
 ON SITE PLAN
  2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.
  
 3. FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A
 SPAN OF 40 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
 NO EXCEPTIONS
  
 _______________________________________________________
 _________
  
 ***ADDITIONAL REQUIREMENTS
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN
 ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS?.
  
 FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY
  
 A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE
 PROVIDED TO APPLICANT
 B. PROVIDE THRESHOLD INSPECTION PLAN
 C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE?
 _______________________________________________________
 _______________
  
  
  
  
  