Plan Review Notes
Plan Review Notes For Permit 19050326
Permit Number 19050326
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-10-01 15:44:33THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) INSTALL AND TEST PER NFPA 110 IF SUPPLYING POWER TO
 ANY LIFE SAFETY EQUIPMENT.
  
 PER NFPA 110
  
 1.1 SCOPE. THIS STANDARD CONTAINS REQUIREMENTS COVERING
 THE
 PERFORMANCE OF EMERGENCY AND STANDBY POWER SYSTEMS
 PROVIDING
 AN ALTERNATE SOURCE OF ELECTRICAL POWER TO LOADS IN
 BUILDINGS
 AND FACILITIES IN THE EVENT THAT THE PRIMARY POWER
 SOURCE
 FAILS.
 1.1.1 POWER SYSTEMS COVERED IN THIS STANDARD INCLUDE
 POWER
 SOURCES, TRANSFER EQUIPMENT, CONTROLS, SUPERVISORY
 EQUIPMENT,
 AND ALL RELATED ELECTRICAL AND MECHANICAL AUXILIARY AND
 ACCESSORY
 EQUIPMENT NEEDED TO SUPPLY ELECTRICAL POWER TO THE LOAD
 TERMINALS OF THE TRANSFER EQUIPMENT.
 1.1.2 THIS STANDARD COVERS INSTALLATION, MAINTENANCE,
 OPERATION,
 AND TESTING REQUIREMENTS AS THEY PERTAIN TO THE
 PERFORMANCE
 OF THE EMERGENCY POWER SUPPLY SYSTEM (EPSS).
  
 1.1.3 THIS STANDARD DOES NOT COVER THE FOLLOWING:
 (1) APPLICATION OF THE EPSS
 (2) EMERGENCY LIGHTING UNIT EQUIPMENT
 (3) DISTRIBUTION WIRING
 (4) UTILITY SERVICE WHEN SUCH SERVICE IS PERMITTED AS
 THE EPSS
 (5) PARAMETERS FOR STORED ENERGY DEVICES
 (6) THE EQUIPMENT OF SYSTEMS THAT ARE NOT CLASSED AS
 LEVEL 1
 OR LEVEL 2 SYSTEMS IN ACCORDANCE WITH CHAPTER 4 OF THIS
 STANDARD
  
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL