Plan Review Notes
Plan Review Notes For Permit 19050305
Permit Number 19050305
Review Stop P
Sequence Number 2
Notes
Date Text
2019-07-09 12:42:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 SECOND REQUEST:
 1. NOT REQUIRED THE COFFEE AND CASHWRAP (BACKWRAP) SINK
 ARE NOT SHOWN AS ACCESSIBLE AND ARE BOTH LIST AS SNK-2
 (HS-2). PROVIDE CLEAR FLOOR SPACE AND COUNTER TOP
 DETAIL FOR BOTH SINKS, SHOWING MAX 34". FBC-ACC 606.2,
 606.3.
 NOTE THAT CLEAR FLOOR SPACE HAS BEEN PROVIDED FOR BOTH
 FIXTURES, BUT DETAIL 7/A9.5 EXCEEDS THE MAXIMUM 34?
 HEIGHT REQUIREMENTS FOR THE BACKWRAP SINK.
  
 2. NOT REQUIRED THE TWO COMPARTMENT SINK LOCATED IN THE
 CLASS ROOM KITCHEN SHALL BE ACCESSIBLE AS IT WOULD BE A
 COMMON USE SINK. PROVIDE CLEAR FLOOR SPACE AND MAX
 HEIGHT DETAIL MAX 34". FBC-ACC 606.2, 606.3
  
 3. THE INTERCEPTOR SHOWN AND NOTED ON PLAN SHEET P1.01
 HAS A CAPACITY THAT EXCEEDS THE MAXIMUM SIZE OF A
 CONCRETE GRAVITY TANK WHICH WOULD BE CONSTRUCTED IN
 ACCORDANCE WITH FAC 64E-6 (SEE CITY OF WPB PUBLIC
 UTILITIES DEPT. STD DETAIL GS-7), SO IT SHOULD BE A
 HYDRO MECHANICAL INTERCEPTOR AND BE SIZED AND
 CONSTRUCTED IN ACCORDANCE WITH PDI G101 (SEE CITY OF
 WPB PUBLIC UTILITIES DEPT. STD DETAIL GS-7.1). PROVIDE
 SPECS FOR EXISTING 2,025 GALLON INTERCEPTOR AND
 CALCULATIONS IN ACCORDANCE WITH THE APPLICABLE
 STANDARD, NOTING THE EXISTING LOAD UPSTREAM OF THE NEW
 WORK AND CALCULATIONS FOR THE NEW WORK. WPB FBC 107.3.5
  
  
 NEW COMMENTS
 1. RE: PLAN SHEET P3.01, DETAIL 1; A SEPARATE BACKFLOW
 PREVENTER IS REQUIRED FOR THE COLD WATER TO THE
 BUILDING FIXTURES AND FOR THE COLD WATER TO THE WATER
 SOFTENER PER FBC PL 608.3.
 2. RE: PLAN SHEET P3.01, DETAIL 7; RUNNING TRAP IS NOT
 ACCEPTABLE PER FBC PL 1002.1.
 A. VENT SHALL RISE VERTICALLY TO MINIMUM 6? ABOVE FLOOD
 LEVEL RIM OF TRAPPED FIXTURE BEFORE OFFSETTING
 HORIZONTALLY PER FBC PL 905.4.
 B. AIR GAP SHALL BE MINIMUM TWICE THE DIAMETER OF THE
 DRAIN PIPE PER FBC PL 802.2.1
 C. FLOOR SINK SHALL BE PROVIDED WITH A WATER SEAL TRAP
 PER FBC PL 802.2
 3. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR DETAIL FOR
 TWO COMPARTMENT SINK SHOWING INDIRECT WASTE DISCHARGING
 SEPARATELY FROM EACH COMPARTMENT TO FLOOR SINK THROUGH
 AN AIR GAP IN ACCORDANCE WITH FBC PL 802.1.1.
 4. PER WPB FBC 107.2.1, PLEASE ADVISE AS TO THE PURPOSE
 OF THE FLOOR SINK LOCATED IN THE FLOOR SPACE BETWEEN
 THE MOP SINK AND THE DISHWASHER.
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050305 700 S ROSEMARY AVE # 116
  