| 2019-07-09 12:42:40 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | SECOND REQUEST: |
| | 1. NOT REQUIRED THE COFFEE AND CASHWRAP (BACKWRAP) SINK |
| | ARE NOT SHOWN AS ACCESSIBLE AND ARE BOTH LIST AS SNK-2 |
| | (HS-2). PROVIDE CLEAR FLOOR SPACE AND COUNTER TOP |
| | DETAIL FOR BOTH SINKS, SHOWING MAX 34". FBC-ACC 606.2, |
| | 606.3. |
| | NOTE THAT CLEAR FLOOR SPACE HAS BEEN PROVIDED FOR BOTH |
| | FIXTURES, BUT DETAIL 7/A9.5 EXCEEDS THE MAXIMUM 34? |
| | HEIGHT REQUIREMENTS FOR THE BACKWRAP SINK. |
| | |
| | 2. NOT REQUIRED THE TWO COMPARTMENT SINK LOCATED IN THE |
| | CLASS ROOM KITCHEN SHALL BE ACCESSIBLE AS IT WOULD BE A |
| | COMMON USE SINK. PROVIDE CLEAR FLOOR SPACE AND MAX |
| | HEIGHT DETAIL MAX 34". FBC-ACC 606.2, 606.3 |
| | |
| | 3. THE INTERCEPTOR SHOWN AND NOTED ON PLAN SHEET P1.01 |
| | HAS A CAPACITY THAT EXCEEDS THE MAXIMUM SIZE OF A |
| | CONCRETE GRAVITY TANK WHICH WOULD BE CONSTRUCTED IN |
| | ACCORDANCE WITH FAC 64E-6 (SEE CITY OF WPB PUBLIC |
| | UTILITIES DEPT. STD DETAIL GS-7), SO IT SHOULD BE A |
| | HYDRO MECHANICAL INTERCEPTOR AND BE SIZED AND |
| | CONSTRUCTED IN ACCORDANCE WITH PDI G101 (SEE CITY OF |
| | WPB PUBLIC UTILITIES DEPT. STD DETAIL GS-7.1). PROVIDE |
| | SPECS FOR EXISTING 2,025 GALLON INTERCEPTOR AND |
| | CALCULATIONS IN ACCORDANCE WITH THE APPLICABLE |
| | STANDARD, NOTING THE EXISTING LOAD UPSTREAM OF THE NEW |
| | WORK AND CALCULATIONS FOR THE NEW WORK. WPB FBC 107.3.5 |
| | |
| | |
| | NEW COMMENTS |
| | 1. RE: PLAN SHEET P3.01, DETAIL 1; A SEPARATE BACKFLOW |
| | PREVENTER IS REQUIRED FOR THE COLD WATER TO THE |
| | BUILDING FIXTURES AND FOR THE COLD WATER TO THE WATER |
| | SOFTENER PER FBC PL 608.3. |
| | 2. RE: PLAN SHEET P3.01, DETAIL 7; RUNNING TRAP IS NOT |
| | ACCEPTABLE PER FBC PL 1002.1. |
| | A. VENT SHALL RISE VERTICALLY TO MINIMUM 6? ABOVE FLOOD |
| | LEVEL RIM OF TRAPPED FIXTURE BEFORE OFFSETTING |
| | HORIZONTALLY PER FBC PL 905.4. |
| | B. AIR GAP SHALL BE MINIMUM TWICE THE DIAMETER OF THE |
| | DRAIN PIPE PER FBC PL 802.2.1 |
| | C. FLOOR SINK SHALL BE PROVIDED WITH A WATER SEAL TRAP |
| | PER FBC PL 802.2 |
| | 3. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR DETAIL FOR |
| | TWO COMPARTMENT SINK SHOWING INDIRECT WASTE DISCHARGING |
| | SEPARATELY FROM EACH COMPARTMENT TO FLOOR SINK THROUGH |
| | AN AIR GAP IN ACCORDANCE WITH FBC PL 802.1.1. |
| | 4. PER WPB FBC 107.2.1, PLEASE ADVISE AS TO THE PURPOSE |
| | OF THE FLOOR SINK LOCATED IN THE FLOOR SPACE BETWEEN |
| | THE MOP SINK AND THE DISHWASHER. |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |