| 2019-05-16 14:46:31 | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | 1) THE COFFEE AND CASHWRAP SINK ARE NOT SHOWN AS |
| | ACCESSIBLE AND ARE BOTH LIST AS SNK-2. PROVIDE CLEAR |
| | FLOOR SPACE AND COUNTER TOP DETAIL SHOWING MAX 34". |
| | FBC-ACC 606.2, 606.3 |
| | |
| | 2) THE 2 COMPARTMENT SINK LOCATED IN THE CLASS ROOM |
| | KITCHEN SHALL BE ACCESSIBLE AS IT WOULD BE A COMMON USE |
| | SINK. PROVIDE CLEAR FLOOR SPACE AND MAX HEIGHT DETAIL |
| | MAX 34". FBC-ACC 606.2, 606.3 |
| | |
| | 3) WATER HEATER DETAIL IS MISSING THE ANTISIPHON VALVE |
| | REQUIRED FOR BOTTOM FEED WATER HEATERS. FBC P 504.1 |
| | |
| | 4) PROVIDE HOW YOU SIZED THE INTERCEPTOR EITHER BY FAC |
| | 64E-6 OR BY THE PDI G101? FBC P1003.1. AND WHAT |
| | MANUFACTURE AND MODEL YOU ARE CALLING FOR. FBC 107.3.5 |
| | |
| | 5) PROVIDE LOCATION ON PLAN OF WHERE GREASE INTERCEPTOR |
| | IS TO BE INSTALLED. FBC P 1003.2 |
| | |
| | 6) PROVIDE NOTE ON PLAN THAT BACKFLOW'S AND GREASE |
| | INTERCEPTOR REQUIRED A SEPARATE PERMIT. WPB AMEND 105.1 |
| | |
| | 7) PROVIDE INSTALLATION MANUAL/ SPECIFICATION SHEETS |
| | FOR THE SOFTENER SYSTEM AND GREASE INTERCEPTOR. FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |