| 2019-06-04 14:30:07 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050305 |
| | ADD: 700 S. ROSEMARY AVE. SUITE: 116 |
| | CONT:TBD/ TO BE DETERMINED |
| | TEL: ???????????????? |
| | E-MAIL; [email protected] AMY HODGSON |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JUNE 4, 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE NONE OF THE ARCHITECTURAL SHEETS |
| | SUBMITTED FOR THIS REVIEW HAVE A DIGITAL SIGNATURE. |
| | PLEASE SHOW COMPLIANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | ARCHITECT DIGITAL SIGNING & SEALING PLANS: |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) THE COVERSHEET A0.1: |
| | 2A). BUILDING CODE INFORMATION INDICATES THE PLANS WERE |
| | DEVELOPED UNDER THE 2014 FBC-B. PLEASE BE AWARE THAT |
| | STATEWIDE THE 2017 FBC FAMILY OF CODES WERE ADOPTED ON |
| | DEC. 31/ 2017. PLEASE UPDATE CODES AND RELEVANT CHANGES |
| | THAT WERE MADE. |
| | |
| | 2B). UNDER THE HEADING OF OCCUPANCY CALCULATIONS THE |
| | RETAIL/ MERCANTILE IS USING AN OCCUPANT LOAD FACTOR OF |
| | 30. PLEASE BE AWARE OF THE CHANGE IN THE 2017 FBC-B |
| | THAT ALL FLOORS ARE TO USE A LOADING FACTOR OF 60. |
| | PLEASE SEE 2017 FBC-B TABLE 1004.1.2. PLEASE UPDATE THE |
| | PLANS. |
| | |
| | 2C. UNDER THE HEADING OF OCCUPANCY CALCULATIONS THE |
| | BUSINESS/ CLASSROOM WE ARE OK WITH THE USAGE OF 30 LOAD |
| | FACTOR, IT IS BETWEEN THE 20 FOR CLASSROOM & 50 FOR |
| | VOCATIONAL ROOMS, IT IS MORE RESTRICTIVE THAN THE LOAD |
| | FACTOR OF 50 FOR VOCATIONAL ROOMS. |
| | |
| | 2D) UNDER THE BUILDING CODE INFORMATION THIS SHEET DOES |
| | NOT PROVIDE IF THIS PLAN WAS DESIGNED AS SEPARATED |
| | OCCUPANCY AND TABLE 508.4 OR IF THE PLAN WAS DESIGNED |
| | AS NONSEPARATED OCCUPANCIES UNDER 508.3 FBC-B. PLEASE |
| | ALSO NOTE THE STORAGE OCCUPANCY DOES NOT INDICATE IF |
| | THE STORAGE OCCUPANCY IS A S1 OR S2 OCCUPANCY. SHEET |
| | 003-A.03 THE CODE PLAN DOES NOT SHOW OCCUPANCY |
| | SEPARATION. |
| | |
| | 3) SHEET 003-A0.3 SHOWS EXIT ACCESS THROUGH A CORRIDOR |
| | 106 TO AN EXIT FROM THE TENANT SPACE. THE PLAN IS |
| | SILENT AS TO WHAT TYPE OF EXIT ENCLOSURE THE OCCUPANTS |
| | ARE ENTERING? PLEASE SEE 2017 FBC-B402.8.6.1. |
| | |
| | 4) NOA 17-0201.03 SERIES SMI-090 ALUMINUM WINDOW WALL |
| | SYSTEM L. M. I., SHEETS 007, 008 & 009. NONE OF THE |
| | DETAILS SHEETS HAVE BEEN MARKED UP TO SHOW CODE |
| | COMPLIANCE. |
| | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 5) NOA 17-0926.16 SUMMIT ALUMINUM ENTRANCE DOOR W/WO |
| | TRANSOM- L.M.I., SHEETS 010, 011, & 012. NONE OF THE |
| | DETAILS SHEETS HAVE BEEN MARKED UP TO SHOW CODE |
| | COMPLIANCE. |
| | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6) SHEET 061-S1.1 UNDER THE HEADING GENERAL STRUCTURAL |
| | NOTES: |
| | 6A) BUILDING CODE. THE BUILDING CODE DATA NEEDS TO BE |
| | UPDATED. THESE PLANS WERE LAST USED IN THE CITY OF |
| | JACKSONVILLE, WITH THEIR LOCAL AMENDMENTS, PLEASE |
| | UPDATE PLANS. |
| | |
| | 6B) UNDER THE HEADING OF WIND, ONLY A PARTIAL WIND |
| | DESIGN DATA WAS INCLUDED. THE MEAN ROOF HEIGHT IS NOT |
| | GIVEN, NEGATIVE PRESSURES ARE ALWAYS TAKEN FROM THE |
| | MEAN ROOF HEIGHT. |
| | |
| | 6C) THE STOREFRONT DESIGN WIND PRESSURE IS GIVEN AT 68 |
| | PSF. THE PLAN DOES NOT STATE IF THIS PRESSURE IS IN |
| | VULT OR VASD. THE PLAN ALSO DOES NOT INCLUDE AT WHAT |
| | EFFECTIVE WIND AREA OR TRIBUTARY AREA THIS PRESSURE IS |
| | GOOD FOR NOR DOES THE PLAN INDICATE IF THIS FOR AN |
| | INTERIOR WALL ZONE (4) OR IF THE GIVEN PRESSURES IS FOR |
| | AN EXTERIOR OR END WALL ZONE(5). NON ENOUGH INFORMATION |
| | TO DETERMINE CODE COMPLIANCE. PLEASE PROVIDE PRESSURES |
| | IN CHART FORM 10 SQ. FT. 20 SQ. FT. 50 SQ. FT. 50 SQ. |
| | FT. & 100 SQ. FT. AND IN VASD SINCE THE PRODUCT |
| | APPROVAL PRESSURES ARE IN VASD. |
| | 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS FOR |
| | HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 7) AT THE TIME OF EITHER THE STEEL FRAMING INSPECTION |
| | OR WINDOW BUCK INSPECTION PLEASE PROVIDE THE FOLLOWING: |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | |
| | 8A)(1) SHEET 014-A2.1 FLOOR AND FINISH PLAN THE TENANT |
| | WALLS THAT BACK UP TO THE EXIT PASSAGEWAY SHOW ON THE |
| | FLOOR PLAN 1 HOUR RATING WALL IDENTIFICATION TAGS A & |
| | E. THE PERIMETER WALL (EXIT PASSAGEWAY) SHOWS WALL |
| | TYPES A & A4 AS ONE HOUR RATED BUT SHEET 026-A9.1 DOES |
| | NOT SHOW THE A TYPE WALLS AS 1 HOUR RATED. 2017 FBC-B |
| | 402.6.8.1, & 1024.3. |
| | |
| | 8A)(2) SHEET 014-A2.1 FLOOR AND FINISH PLAN THE TENANT |
| | WALLS THAT BACK UP TO THE EXIT PASSAGEWAY SHOW ON THE |
| | FLOOR PLAN 1 HOUR RATING WALL IDENTIFICATION TAG E. THE |
| | PERIMETER WALL (EXIT PASSAGEWAY) SHOWS WALL TYPES E & |
| | E1 AS ONE HOUR RATED BUT SHEET 026-A9.1 DOES SHOW THE E |
| | TYPE WALLS AS 1 HOUR RATED BUT THERE IS NO UL RATING OR |
| | GYPSUM ASSOCIATION RATING SHOWN. 2017 FBC-B 402.6.8.1, |
| | & 1024.3. |
| | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |