2019-06-04 14:30:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050305
 ADD: 700 S. ROSEMARY AVE. SUITE: 116
 CONT:TBD/ TO BE DETERMINED
 TEL: ????????????????
 E-MAIL; [email protected] AMY HODGSON
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 4, 2019
 ACTION: DENIED
  
 1) PLEASE NOTE NONE OF THE ARCHITECTURAL SHEETS
 SUBMITTED FOR THIS REVIEW HAVE A DIGITAL SIGNATURE.
 PLEASE SHOW COMPLIANCE WITH FLORIDA ADMINISTRATIVE CODE
 ARCHITECT DIGITAL SIGNING & SEALING PLANS:
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE COVERSHEET A0.1:
 2A). BUILDING CODE INFORMATION INDICATES THE PLANS WERE
 DEVELOPED UNDER THE 2014 FBC-B. PLEASE BE AWARE THAT
 STATEWIDE THE 2017 FBC FAMILY OF CODES WERE ADOPTED ON
 DEC. 31/ 2017. PLEASE UPDATE CODES AND RELEVANT CHANGES
 THAT WERE MADE.
  
 2B). UNDER THE HEADING OF OCCUPANCY CALCULATIONS THE
 RETAIL/ MERCANTILE IS USING AN OCCUPANT LOAD FACTOR OF
 30. PLEASE BE AWARE OF THE CHANGE IN THE 2017 FBC-B
 THAT ALL FLOORS ARE TO USE A LOADING FACTOR OF 60.
 PLEASE SEE 2017 FBC-B TABLE 1004.1.2. PLEASE UPDATE THE
 PLANS.
  
 2C. UNDER THE HEADING OF OCCUPANCY CALCULATIONS THE
 BUSINESS/ CLASSROOM WE ARE OK WITH THE USAGE OF 30 LOAD
 FACTOR, IT IS BETWEEN THE 20 FOR CLASSROOM & 50 FOR
 VOCATIONAL ROOMS, IT IS MORE RESTRICTIVE THAN THE LOAD
 FACTOR OF 50 FOR VOCATIONAL ROOMS.
  
 2D) UNDER THE BUILDING CODE INFORMATION THIS SHEET DOES
 NOT PROVIDE IF THIS PLAN WAS DESIGNED AS SEPARATED
 OCCUPANCY AND TABLE 508.4 OR IF THE PLAN WAS DESIGNED
 AS NONSEPARATED OCCUPANCIES UNDER 508.3 FBC-B. PLEASE
 ALSO NOTE THE STORAGE OCCUPANCY DOES NOT INDICATE IF
 THE STORAGE OCCUPANCY IS A S1 OR S2 OCCUPANCY. SHEET
 003-A.03 THE CODE PLAN DOES NOT SHOW OCCUPANCY
 SEPARATION.
  
 3) SHEET 003-A0.3 SHOWS EXIT ACCESS THROUGH A CORRIDOR
 106 TO AN EXIT FROM THE TENANT SPACE. THE PLAN IS
 SILENT AS TO WHAT TYPE OF EXIT ENCLOSURE THE OCCUPANTS
 ARE ENTERING? PLEASE SEE 2017 FBC-B402.8.6.1.
  
 4) NOA 17-0201.03 SERIES SMI-090 ALUMINUM WINDOW WALL
 SYSTEM L. M. I., SHEETS 007, 008 & 009. NONE OF THE
 DETAILS SHEETS HAVE BEEN MARKED UP TO SHOW CODE
 COMPLIANCE.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) NOA 17-0926.16 SUMMIT ALUMINUM ENTRANCE DOOR W/WO
 TRANSOM- L.M.I., SHEETS 010, 011, & 012. NONE OF THE
 DETAILS SHEETS HAVE BEEN MARKED UP TO SHOW CODE
 COMPLIANCE.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET 061-S1.1 UNDER THE HEADING GENERAL STRUCTURAL
 NOTES:
 6A) BUILDING CODE. THE BUILDING CODE DATA NEEDS TO BE
 UPDATED. THESE PLANS WERE LAST USED IN THE CITY OF
 JACKSONVILLE, WITH THEIR LOCAL AMENDMENTS, PLEASE
 UPDATE PLANS.
  
 6B) UNDER THE HEADING OF WIND, ONLY A PARTIAL WIND
 DESIGN DATA WAS INCLUDED. THE MEAN ROOF HEIGHT IS NOT
 GIVEN, NEGATIVE PRESSURES ARE ALWAYS TAKEN FROM THE
 MEAN ROOF HEIGHT.
  
 6C) THE STOREFRONT DESIGN WIND PRESSURE IS GIVEN AT 68
 PSF. THE PLAN DOES NOT STATE IF THIS PRESSURE IS IN
 VULT OR VASD. THE PLAN ALSO DOES NOT INCLUDE AT WHAT
 EFFECTIVE WIND AREA OR TRIBUTARY AREA THIS PRESSURE IS
 GOOD FOR NOR DOES THE PLAN INDICATE IF THIS FOR AN
 INTERIOR WALL ZONE (4) OR IF THE GIVEN PRESSURES IS FOR
 AN EXTERIOR OR END WALL ZONE(5). NON ENOUGH INFORMATION
 TO DETERMINE CODE COMPLIANCE. PLEASE PROVIDE PRESSURES
 IN CHART FORM 10 SQ. FT. 20 SQ. FT. 50 SQ. FT. 50 SQ.
 FT. & 100 SQ. FT. AND IN VASD SINCE THE PRODUCT
 APPROVAL PRESSURES ARE IN VASD.
 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 7) AT THE TIME OF EITHER THE STEEL FRAMING INSPECTION
 OR WINDOW BUCK INSPECTION PLEASE PROVIDE THE FOLLOWING:
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 8A)(1) SHEET 014-A2.1 FLOOR AND FINISH PLAN THE TENANT
 WALLS THAT BACK UP TO THE EXIT PASSAGEWAY SHOW ON THE
 FLOOR PLAN 1 HOUR RATING WALL IDENTIFICATION TAGS A &
 E. THE PERIMETER WALL (EXIT PASSAGEWAY) SHOWS WALL
 TYPES A & A4 AS ONE HOUR RATED BUT SHEET 026-A9.1 DOES
 NOT SHOW THE A TYPE WALLS AS 1 HOUR RATED. 2017 FBC-B
 402.6.8.1, & 1024.3.
  
 8A)(2) SHEET 014-A2.1 FLOOR AND FINISH PLAN THE TENANT
 WALLS THAT BACK UP TO THE EXIT PASSAGEWAY SHOW ON THE
 FLOOR PLAN 1 HOUR RATING WALL IDENTIFICATION TAG E. THE
 PERIMETER WALL (EXIT PASSAGEWAY) SHOWS WALL TYPES E &
 E1 AS ONE HOUR RATED BUT SHEET 026-A9.1 DOES SHOW THE E
 TYPE WALLS AS 1 HOUR RATED BUT THERE IS NO UL RATING OR
 GYPSUM ASSOCIATION RATING SHOWN. 2017 FBC-B 402.6.8.1,
 & 1024.3.
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  