| 2020-01-07 08:08:10 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050303 |
| | ADD: 3601 S DIXIE HWY |
| | CONT: J & V SERVICES |
| | TEL: 561-601-1614 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: TUES. JAN. 07/ 2020 |
| | ACTION: DENIED |
| | |
| | *******************4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) ************************** |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1A) COMPLIED. |
| | |
| | 1B) 4TH REQUEST. THE PERMIT APPLICATION INDICATES UNDER |
| | THE DESCRIPTION OF WORK, CHANGED(WHITE OUT) THIS REVIEW |
| | TO EXISTING SINK ON THE BATHROOM. THE PREVIOUS REVIEWS |
| | STATED: INTERIOR REMODELING AND THE INSTALLATION OF A |
| | NEW BATHROOM SINK. THERE HAS BEEN A HOLD AND 4 X FEE |
| | FOR WORK WITHOUT A PERMIT SINCE 4/22/2019 FOR BUILDING, |
| | NEW WALLS, ELECTRIC AND PLUMBING. THE PLANS INDICATE |
| | OFFICE AS BUILT BUT THERE IS NO SINK SHOWN ON THE |
| | PLANS!!!!!! THE PLANS READ AS BUILT BUT SHOULD READ NEW |
| | WORK (NOT PERMITTED)!!!!! |
| | COMMENT FROM THE PREVIOUS REVIEWS 1-3. |
| | SHEET A-101 LIST IN DETAIL # 1 INDICATES 2 NEW OFFICES |
| | AND NO RESTROOM OR NEW BATHROOM SINK? A RED TAG WAS |
| | WRITTEN AND LISTED IN COMPUTER ON 4/22/19 FOR NEW |
| | WALLS, ELECTRIC AND PLUMBING. THERE ARE NO PLUMBING |
| | SHEETS INCORPORATED IN THESE PLANS? ADDITIONAL |
| | INFORMATION IS REQUIRED, A DISCREPANCY IN PLANS AND THE |
| | RED TAG WRITTEN ON 04/22/19 FOR WORK TO BE COVERED |
| | UNDER THIS PERMIT, DISCREPANCY OF DESCRIPTION OF WORK. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) PLUMBING PASSED BUT THE PLANS A SHEETS STILL SHOW |
| | NEW WORK OFFICES BEING BUILT PLUS E SHEETS AS BUILT |
| | ADDITIONAL CEILING FANS AND OUTLETS ADDED. THIS IS NOT |
| | ONLY A SINK BEING CHANGED OUT. AS BUILT SHOULD READ NEW |
| | WORK (NOT PERMITTED)!!!!!!!!!! |
| | |
| | 3) 4TH REQUEST. NO MECHANICAL PLANS WERE SUBMITTED A |
| | REVIEW STOP WAS ADDED BUT COMPLIANCE FOR TOILET ROOMS |
| | WOULD BE REQUIRED UNDER THE 2017 MECHANICAL CODE |
| | SECTION 403.3.2.3 LOCAL EXHAUST, AND TABLE 403.3.1.1 |
| | PUBLIC SPACES, TOILET ROOM?S FOOTNOTE (G). |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |