| Date |
Text |
| 2019-07-02 08:44:15 | PREVIOUS COMMENTS: |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(4) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS WHEN THE |
| | FIRE ALARM JOB VALUE EXCEEDS $5,000. |
| | |
| | PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW |
| | SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO |
| | THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER |
| | ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| | |
| | NFPA 72 2013 EDITION |
| | 7.4 SHOP DRAWINGS (INSTALLATION DOCUMENTATION). |
| | 7.4.5 FLOOR PLAN DRAWINGS SHALL BE DRAWN TO AN |
| | INDICATED SCALE |
| | AND SHALL INCLUDE THE FOLLOWING INFORMATION, WHERE |
| | APPLICABLE |
| | FOR THE PARTICULAR SYSTEM: |
| | (1) FLOOR OR LEVEL IDENTIFICATION |
| | (2) POINT OF COMPASS (INDICATION OF NORTH) |
| | (3) GRAPHIC SCALE |
| | (4) ALL WALLS AND DOORS |
| | (5) ALL PARTITIONS EXTENDING TO WITHIN 15 PERCENT OF |
| | THE CEILING |
| | HEIGHT (WHERE APPLICABLE AND WHEN KNOWN) |
| | (6) ROOM AND AREA DESCRIPTIONS |
| | (7) SYSTEM DEVICES/COMPONENT LOCATIONS |
| | (8) LOCATIONS OF FIRE ALARM PRIMARY POWER DISCONNECTING |
| | MEANS |
| | (9) LOCATIONS OF MONITOR/CONTROL INTERFACES TO OTHER |
| | SYSTEMS |
| | (10) SYSTEM RISER LOCATIONS |
| | (11) TYPE AND NUMBER OF SYSTEM COMPONENTS/DEVICES ON |
| | EACH CIRCUIT, ON EACH FLOOR OR LEVEL |
| | (12) TYPE AND QUANTITY OF CONDUCTORS AND CONDUIT (IF |
| | USED) |
| | FOR EACH CIRCUIT |
| | (13) IDENTIFICATION OF ANY CEILING OVER 10 FT (3.0 M) |
| | IN HEIGHT |
| | WHERE AUTOMATIC FIRE DETECTION IS BEING PROPOSED |
| | (14) DETAILS OF CEILING GEOMETRIES, INCLUDING BEAMS AND |
| | SOLID |
| | JOISTS, WHERE AUTOMATIC FIRE DETECTION IS BEING |
| | PROPOSED |
| | (15) WHERE KNOWN, ACOUSTIC PROPERTIES OF SPACES |
| | |
| | A CERTIFICATE OF COMPLETION AND A THIRD PARTY |
| | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL |
| | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. |
| | |
| | ADDITIONAL COMMENTS: |
| | THE RESUBMITTED PLANS FAILED: |
| | THE CONTRACTOR OF RECORD RESPONSIBLE FOR THE SYSTEM |
| | DESIGN SHALL TAKE OWNERSHIP OF THE PLANS BY PROVIDING A |
| | SIGNATURE FROM THE QUALIFIED DESIGNER, THE LICENSE |
| | NUMBER, AND THE COMPANY NAME ON THE PLANS. |
| | |
| | THE PLANS SHOWS A CLOUD INDICATING THE NEW DEVICE BUT |
| | DOESNT PROVIDE THE LOCATION OF WHERE THIS DEVICES WILL |
| | BE PLACED. IDENTIFY FLOOR LEVEL, GRAPHIC SCALE, WALLS |
| | AND DOORS, ROOM AND AREA DESCRIPTION,THE LOCATION OF |
| | FIRE ALARM PRIMARY POWER DISCONNECTING MEANS, AND |
| | LOCATION OF THE MONITOR/CONTROL INTERFACES TO OTHER |
| | SYSTEM |
| | |
| | |