Plan Review Notes
Plan Review Notes For Permit 19050301
Permit Number 19050301
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-07-02 08:44:15PREVIOUS COMMENTS:
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(4) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS WHEN THE
 FIRE ALARM JOB VALUE EXCEEDS $5,000.
  
 PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW
 SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO
 THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER
 ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 NFPA 72 2013 EDITION
 7.4 SHOP DRAWINGS (INSTALLATION DOCUMENTATION).
 7.4.5 FLOOR PLAN DRAWINGS SHALL BE DRAWN TO AN
 INDICATED SCALE
 AND SHALL INCLUDE THE FOLLOWING INFORMATION, WHERE
 APPLICABLE
 FOR THE PARTICULAR SYSTEM:
 (1) FLOOR OR LEVEL IDENTIFICATION
 (2) POINT OF COMPASS (INDICATION OF NORTH)
 (3) GRAPHIC SCALE
 (4) ALL WALLS AND DOORS
 (5) ALL PARTITIONS EXTENDING TO WITHIN 15 PERCENT OF
 THE CEILING
 HEIGHT (WHERE APPLICABLE AND WHEN KNOWN)
 (6) ROOM AND AREA DESCRIPTIONS
 (7) SYSTEM DEVICES/COMPONENT LOCATIONS
 (8) LOCATIONS OF FIRE ALARM PRIMARY POWER DISCONNECTING
 MEANS
 (9) LOCATIONS OF MONITOR/CONTROL INTERFACES TO OTHER
 SYSTEMS
 (10) SYSTEM RISER LOCATIONS
 (11) TYPE AND NUMBER OF SYSTEM COMPONENTS/DEVICES ON
 EACH CIRCUIT, ON EACH FLOOR OR LEVEL
 (12) TYPE AND QUANTITY OF CONDUCTORS AND CONDUIT (IF
 USED)
 FOR EACH CIRCUIT
 (13) IDENTIFICATION OF ANY CEILING OVER 10 FT (3.0 M)
 IN HEIGHT
 WHERE AUTOMATIC FIRE DETECTION IS BEING PROPOSED
 (14) DETAILS OF CEILING GEOMETRIES, INCLUDING BEAMS AND
 SOLID
 JOISTS, WHERE AUTOMATIC FIRE DETECTION IS BEING
 PROPOSED
 (15) WHERE KNOWN, ACOUSTIC PROPERTIES OF SPACES
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 ADDITIONAL COMMENTS:
 THE RESUBMITTED PLANS FAILED:
 THE CONTRACTOR OF RECORD RESPONSIBLE FOR THE SYSTEM
 DESIGN SHALL TAKE OWNERSHIP OF THE PLANS BY PROVIDING A
 SIGNATURE FROM THE QUALIFIED DESIGNER, THE LICENSE
 NUMBER, AND THE COMPANY NAME ON THE PLANS.
  
 THE PLANS SHOWS A CLOUD INDICATING THE NEW DEVICE BUT
 DOESNT PROVIDE THE LOCATION OF WHERE THIS DEVICES WILL
 BE PLACED. IDENTIFY FLOOR LEVEL, GRAPHIC SCALE, WALLS
 AND DOORS, ROOM AND AREA DESCRIPTION,THE LOCATION OF
 FIRE ALARM PRIMARY POWER DISCONNECTING MEANS, AND
 LOCATION OF THE MONITOR/CONTROL INTERFACES TO OTHER
 SYSTEM
  
  
 BRITTANY WOODS
 FIRE INSPECTOR/ FIRE INVESTIGATOR
 OFFICE OF FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 561-804-4754
  