| 2019-05-15 08:15:14 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E2.1 |
| | |
| | 1) GFCI PROTECTION IN BATHROOMS ALL OUTLETS WITHIN 6 OF |
| | SINK, SHOWER, BATH TUB TO BE GFCI PROTECTED. |
| | |
| | 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL |
| | GROUND -FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL SHALL |
| | BE PROVIDED AS REQUIRED IN 210.8(A) THROUGH (D). THE |
| | GROUNDFAULT |
| | CIRCUIT-INTERRUPTER SHALL BE INSTALLED IN A READILY |
| | ACCESSIBLE |
| | LOCATION. |
| | |
| | (7) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 |
| | M |
| | (6 FT) OF THE OUTSIDE EDGE OF THE SINK |
| | |
| | (9) BATHTUBS OR SHOWER STALLS ? WHERE RECEPTACLES ARE |
| | INSTALLED WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE OF |
| | THE |
| | BATHTUB OR SHOWER STALL |
| | |
| | 20 AFCI PROTECTION REQUIRED IN LAUNDRY AND KITCHEN |
| | AREAS, GFCI PROTECTION AS WELL |
| | |
| | 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | ARC-FAULT CIRC UIT-INTERRUPTER PROTECTION SHALL BE |
| | PROVIDED AS |
| | REQUIRED IN 210.12(A) (B), AND (C). THE ARC-FAULT |
| | CIRCUIT INTERRUPTER |
| | SHALL BE INSTALLED IN A READILY ACCESSIBLE LOCATION. |
| | (A) DWELLING UNITS. ALL 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPE RE BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES |
| | INSTALLED |
| | IN DWELLING UNIT KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION |
| | ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS, OR SIMILAR |
| | ROOMS OR AREAS |
| | SHALL BE PROTECTED BY ANY OF THE MEANS DESCRIBED IN |
| | 210.12(A) |
| | (1) THROUGH (6): |
| | |
| | 3) OUTLET SPACING TO MEET 210.52 ALL AREAS |
| | |
| | PAGE E3.1 |
| | |
| | 1) FIXTURES SHOWN OVER THE SHOWER STALLS IN MASTER BATH |
| | TO BE LISTED FOR THE AREA |
| | |
| | 110.3 ( B) INSTALLATION AND USE. LISTED OR LABELED |
| | EQUIPMENT SHALL BE |
| | INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS |
| | INCLUDED |
| | IN THE LISTING OR LABELING. |