2019-05-15 09:07:02FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 RISER ON PAGE E4.1 SHOWS 800 AMPERE MAIN WITH 620
 AMPERES OF CONDUCTOR.
  
 230.31 SIZE AND RATING
 (A) GENERAL. UNDERGROUND SERVICE CONDUCTORS SHALL HAVE
 SUFFICIENT
 AMPACITY TO CARRY THE CURRENT FOR THE LOAD AS
 CALCULATED IN
 ACCORDANC E WITH ARTICLE 220 AND S HALL HAVE ADEQUATE
 MECHANICAL
 STRENGTH.