| Plan Review Notes For Permit 19050266 |
| Permit Number |
19050266 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-11 09:45:01 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | | 805-6724 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SUBMITTED DRAWING DETAILS FOR METAL ADA RAIL-RAMP | | | SECTION AND DRAWING DETAIL FOR TYPICAL ADA METAL RAIL | | | SECTION MUST SHOW COMPLIANCE TO SECTION 505 OF | | | FBC-ACCESSIBILITY AND 405.9 OF FBC-ACCESSIBILITY. | | | 2. PROVIDE A DRAWING DETAIL OF THE PROPOSED STAIR | | | SHOWING CONSTRUCTION METHOD ALONG WITH REQUIRED | | | HANDRAILS COMPLYING WITH SECTION 505 OF | | | FBC-ACCESSIBILITY. | | | |
|