Plan Review Notes
Plan Review Notes For Permit 19050248
Permit Number 19050248
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2019-05-06 14:03:09ELEVATION CERTIFICATE REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REFERENCE SECTION A6 OF ELEVATION CERTIFICATE (EC)
 AND ITEM A6 (PAGE 1 OF 9) OF THE INSTRUCTIONS FOR
 COMPLETING THE ELEVATION CERTIFICATE.
 ADDITIONAL PICTURES ARE REQUIRED BASED ON THE
 INSTALATION OF FLOOD OPENINGS AND STRUCTURE IS
 MULTI-STORY.
  
 2. REFERENCE SECTION A9 (A), (B) & (C) OF THE ELEVATION
 CERTIFICATE.
 A9 (A) STATES SQUARE FOOTAGE OF GARAGE IS 512 SQ/FT.
 APPROVED GROUND FLOOR PLAN STATES SQUARE FOOTAGE OF
 GARAGE IS 462 SQ/FT. PLEASE CLARIFY.
 A9 (B) STATES NUMBER OF PERMANENT FLOOD OPENINGS
 INSTALLED ABOVE ADJACENT GRADE IS 2. APPROVED GROUND
 FLOOR PLAN INDICTES 4 NON-ENGINEERED FLOOD OPENINGS
 SHALL BE INSTALLED ABOVE GARAGE FINISH FLOOR WITH A NET
 OPENING OF 128 SQ/INCHES FOR A TOTAL OF 512 SQ/INCHES.
 IF THE INTERIOR GRADE ELEVATION IS USED, NOTE THIS IN
 THE COMMENTS AREA OF SECTION D. PLEASE CLARIFY.
 A9(C) STATES NET AREA OF FLOOD OPENINGS IN A9 (B) IS
 512 SQ/INCHES. APPROVED GROUND FLOOR PLAN STATES 4
 OPENINGS WILL PROVIDE 512 SQ/INCHES OF FLOOD OPENING.
 PLEASE CLARIFY.
  
 3. PROVIDE DETAIL OF THE NON-ENGINEERED FLOOD OPENINGS.
 4. PROVIDE PICTURES OF INSTALLED FLOOD VENTS.
 5. PROVIDE PICTURES OF MECHANICAL EQUIPMENT.
  
 ALL PHOTOS SHALL BE IN COLOR
  
  