| 2019-08-13 08:41:37 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR |
| | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| | 107.1, 107.2.1, 107.3.5.1.2 (A DIGITAL PLAN REQUIRES A |
| | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY |
| | VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS |
| | 471/481) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 (NOT PROVIDED.) |
| | 5. CORRECTED. |
| | 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND |
| | ELECTRICAL PANEL TO CONFIRM CODE COMPLIANCE. WPB FBC |
| | 107.2.1 (LOCATION OF SERVICE NOT PROVIDED.) |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 9NOT |
| | PROVIDED. PLAN SHOWS DETAILS FROM THE 1993 NEC, WHICH |
| | IS NOT THE CURRENT CODE. ALSO, RISER DIAGRAM QUOTES NEC |
| | 250.81, WHICH DOES NOT EXIST. PROVIDE UPDATES TO THESE |
| | ITEMS AND PROVIDE THE IBTP PER COMMENT.) |
| | 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE |
| | INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN |
| | DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC |
| | RE E3610.4 (NOT CORRECTED.) |
| | 9. CORRECTED. |
| | 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 ( NOT |
| | CORRECT. A SMOKE ALARM IS REQUIRED OUTSIDE THE SLEEPING |
| | AREA, AND A CARBON MONOXIDE ALARM IS REQUIRED WITHIN 10 |
| | FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE |
| | R315.1) |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |